background image

decimal points for a few seconds while the new
information is stored in permanent memory.

All new BA578C indicators are supplied calibrated
as requested at the time of ordering.  If calibration
is not requested, the transmitter will be set for 3
wire RTD input with 4 to 20mA output correspond-
ing to a display of 0.0°C to 100.0°C.

5.1 Summary of Programme Menu functions

The parameters which may be programmed vary
depending upon which input is selected.  For:

Thermocouple and resistance 
thermometer inputs 

The BA578C transmitter will always display
sensor temperature.  Programming allows the
display to be in degrees centigrade or Fahren-
heit, and for the display resolution to be
selected.

Zero and span of the 4/20mA output current
may be programmed to represent any display
range.

Voltage input

The display may be programmed to show the
input  voltage in any engineering units.

Zero and span of the 4/20mA output current
may be independently programmed to repre-
sent any displayed value. 

Each of the functions in the Programme Menu is
described in the following summary with a cross
reference to more detailed information.   Figs 5A
and 5B illustrate the location of each function within
the menu.  

 

Display        Summary of Programme Menu

                                         functions

'InPut'

Transmitter input

Conditions the transmitter to accept
thermocouple 'tHC', resistance
thermometer 'rtd' or a voltage 'UOLt'
input.
See section 5.2.1

For Thermocouple Inputs

'tYPE'

Sensor type

Selects the type of thermocouple input.
See section 5.3.1

'dEg'

Units of display

Sets display to 

o

C or

 o

F.

See section 5.3.2

'rESn'

Display resolution

Selects low or high display resolution.
See section 5.3.3

'CJC'

Cold junction compensation

Turns thermocouple cold junction
compensation ON or OFF.
See section 5.3.4

'burn'

Input open circuit drive

Selects up scale drive, down scale drive
or no drive when input is open circuit. 
See section 5.3.5

For Resistance Thermometer Inputs

'tYPE'

Sensor type

Selects 3-wire, 4-wire or differential
Pt100 resistance thermometer input.
See section 5.4.1

'dEg'

Units of display

Sets display to 

o

C or

 o

F.

See section 5.4.2

'rESn'

Display resolution

Selects low or high display resolution.

See section 5.4.3

      7

Summary of Contents for BA578C

Page 1: ...Issue 4 26th September 2008 BA578C panel mounting indicating temperature transmitter issue 4...

Page 2: ...eferences 5 8 1 Conditioning internal references 5 8 2 Voltage input reference 5 8 3 3 wire RTD reference 5 8 4 4 wire RTD reference 5 8 5 Output current reference 6 Trim Menu 6 1 Calibration procedur...

Page 3: ...ions of Section 5 you will find information on setting up for Section 6 3 Themocouple input Section 6 4 Resistance thermometer input Section 6 5 Voltage input A word of warning Section 5 8 explains ho...

Page 4: ...the 4 20mA output current The transmitter and the optional alarms are powered from the 4 20mA current loop but the optional display backlight requires a separate supply Each time power is applied to...

Page 5: ...sed in a robust aluminium enclosure with a polyester front panel and Noryl bezel The front panel provides IP65 protection and a gasket seals the joint between the instrument and the panel The transmit...

Page 6: ...are contained in section 6 which also describes periodic calibration When the transmitter is fitted with alarms additional functions are added to the programme menu These are described in section 10...

Page 7: ...value Each of the functions in the Programme Menu is described in the following summary with a cross reference to more detailed information Figs 5A and 5B illustrate the location of each function wit...

Page 8: ...8...

Page 9: ...9...

Page 10: ...st be entered to gain access to the programme and the trim menus Default code 0000 disables the security function and allows unrestricted access to all functions in the programme and trim menus See se...

Page 11: ...to the sub menu 5 3 5 Input open circuit drive burn If the thermocouple fails and becomes open circuit the transmitter can be conditioned to drive the display and the 4 20mA output current up or down...

Page 12: ...xt digit When the least significant digit has been adjusted press E to return to the dISP prompt 5 5 3 High input display calibration In HI This function defines the higher voltage input and the corre...

Page 13: ...ned to the display mode If the security code is lost access to the Programme and Trim Menus can be obtained by putting the internal security link in the override position see Fig 6 The security code c...

Page 14: ...mitters may be calibrated in a workshop Select 3rtd from the Cond sub menu and press P The transmitter will display scrolling decimal points while the reference is being updated followed by Ent prior...

Page 15: ...ly trimmed at the bottom of the input range To make the adjust ment connect a calibrator to the transmitter input terminals to simulate minimum input or place the primary element in a vessel at the mi...

Page 16: ...se to full scale The current security code is 1209 The example is divided into two sections Steps 1 to 10 explain how to condition the transmitter and to calibrate the 4 20mA output using the internal...

Page 17: ...may be calibrated by cooling and heating the thermocouple to 10 and 240o C This is the preferred method for routine calibration Step 11 Entering the trim menu Enter the trim menu by simultaneously pr...

Page 18: ...display mode 8 MAINTENANCE 8 1 Fault finding during commissioning If the BA578C transmitter fails to function during commissioning the following procedure should be followed Symptom Cause Solution No...

Page 19: ...any instrument which fails We recommend that suspect instruments are returned to BEKA associates or our local agent for repair 8 4 Guarantee Transmitters which fail within the guarantee period should...

Page 20: ...with a thermally printed tag strip on the rear panel with any legend containing up to 35 alphanumeric characters This strip is not visible from the front of the instrument after installation 10 ALARM...

Page 21: ...alarm parameters See section 10 3 1 SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator display equals the setpoint The setpoint can also be adjusted directly fro...

Page 22: ...22 Fig 11 Programme structure for optional alarms...

Page 23: ...ut status select no nc from the alarm sub menu and press P to reveal the current setting The function may be changed by pressing the Up or Down buttons followed by the E button to return the no nc pro...

Page 24: ...AcSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments are supplied with thi...

Page 25: ...installed in a poorly illuminated area The backlight is segregated from the measuring circuit and may be powered from any 18 to 30V dc supply Fig 13 Backlight power supply The brilliance of the displ...

Reviews: