Notes:
1.
The unclassified location equipment connected to the associated nonincendive
field wiring apparatus must not use or generate more than 250V rms or 250V dc.
2.
Nonincendive field wiring installations shall be in accordance with the National
Electrical Code ANSI/NFPA 70. The Nonincendive Field Wiring concept allows
interconnection of Nonincendive Field Wiring Apparatus with Associated
Nonincendive Field Wiring Apparatus using any of the wiring methods permitted for
unclassified locations.
3A.
4.
Apparatus connected to the optional alarm contacts shall be FM Approved as
Associated Nonincendive Field Wiring Apparatus and shall comply with the
following requirements:
Voc
equal to or less than
Vmax
La
equal to or greater than
Li
Ca
equal to or greater than
Ci
5.
Terminals S1 to S7 shall be connected to simple apparatus or volt free contacts of
FM Approved Nonincendive Field Wiring Apparatus or FM Approved Associated
Nonincendive Field Wiring Apparatus installed using Division 2 wiring methods.
6.
To maintain IP65 protection between the BA488CF and the mounti ng panel:
Four panel mounting clips should be used
Minimum panel thickness should be
2mm (0.08inches) Steel
3mm (0.12inches) Aluminium
Outside panel finish should be smooth, free from particle inclusions, runs or
build-up around cut-out.
Panel cut-out should be
66.2 x 136.0mm -0.0 +0.5
(2.60 x 5.35 inches –0.00 +0.02)
Edges of panel cut-out should be deburred and clean
Each panel mounting clip should be
tightened to between:
20 and 22cNm (1.77 to 1.95 inLb)
Cont.
FNICO non-linear power supply
A FNICO non-linear fieldbus power supply shall be:
FM Approved Associated Nonincendive Field Wiring Apparatus installed in the
unclassified location complying with the following table:
OR
FM Approved Nonincendive Field Wiring Apparatus installed in the classified
location complying with the following table:
Voc
V
14
15
16
17
17.5
112
121
mA
274
199
154
432
531
570
360
319
mA
Maximum current
for Groups AB [IIC]
Maximum current
for Groups CD [IIB, IIA]
FM Approved Nonincendive Field Wiring Apparatus installed in the classified
location with parameters complying with the following requirements:
La
Ca
Voc
FM Approved Associated Nonincendive Field Wiring Apparatus installed in the
A linear fieldbus power supply shall be:
Linear power supply
unclassified location with parameters complying with the following requirements:
OR
3B.
equal to or greater than
equal to or greater than
equal to or less than
Vmax
Ci
Li