BEKA BA474ND Installation & Maintenance Instructions Manual Download Page 26

24

10.4.3  Alarm configuration

Alarm configuration may be performed via the
HART

 digital communication, see the BA47XBA67X

Indicating Temperature Transmitter HART

 Interface

Guide which may be downloaded from
www.beka.co.uk/manuals.  Alternatively configuration
may be performed using the configuration menu
which is accessed via the four push buttons located
behind the instrument switch cover, see Fig 5.  When
frequent adjustments are required the transmitter can
be supplied with a keypad mounted on the outside of
this cover.

When a BA474ND indicating temperature transmitter
is supplied with optional alarms the conditioning
menu is extended as shown in Fig 12.   The
additional alarm functions appear between 'bAr' and
'CodE' in the configuration menu.     For  simplicity
Fig 12 only shows the additional sub-functions for
alarm 1, but alarm 2 has identical sub-functions.

The following table summarises each of the alarm
configuration functions and includes a cross
reference to more detailed information.   Again only
the functions for alarm 1 are listed, but alarm 2 has
identical functions.

Summary of programmable alarm functions

   

Display

      Description of function

‘ALr1’ Alarm 

1

‘ALr2’

Alarm 2

The two functions

  e

ach contain seven

identical sub-functions, one set for
configuration alarm 1 and the other for
configuration alarm 2.
See section 10.4.4 and Fig 12.

'EnbL'

Alarm enable

Enables or disables the alarm function
without changing the alarm parameters.
See section  10.4.5

'SP1'

Alarm setpoint 1

Adjusts the alarm setpoint.  The alarm is
activated when the indicator display
equals the setpoint.
See section 10.4.6

'Hi.Lo'

Alarm function

Defines whether the alarm has a high or
low function.
See section 10.4.7

'no.nC'

Normally open or normally closed
output

Determines whether the single pole alarm
output is open or closed in the non-alarm
condition.
See section 10.4.8

'HStr'

Hysteresis

Adjusts the alarm hysteresis.
See section 10.4.9

'dELA'

Alarm delay

 

time

Adjusts the delay between the display
equalling the setpoint and the alarm
output being activated.
See section 10.4.10

'SiL'

Alarm silence time

Defines the time that the alarm output
remains in the non-alarm condition
following acceptance of an alarm.
See section 10.4.11

'ACSP'

Access setpoint

Enables direct access to the alarm
setpoints from the transmitter operational
mode i.e. when it is displaying
temperature.  Access may be protected
by a separate security code.
See section 10.4.12

Summary of Contents for BA474ND

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA474ND...

Page 2: ...fice Cutbush Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB...

Page 3: ...Issue 7 4 th March 2014 BA474ND Type n certified field mounting indicating temperature transmitter with intrinsically safe sensor input Issue 7...

Page 4: ...f bargraph display bAr 7 2 9 Access code CodE 7 2 10 Resistance thermometer type r tYPE 7 2 11 Decimal point position dP 7 2 12 Lower input display in Lo 7 2 13 Higher input display in Hi 7 3 Default...

Page 5: ...ormation for IECEx installations and for use in combustible dust atmospheres is contained in appendices to this manual The transmitter is HART Registered and is compliant with HART protocol standard r...

Page 6: ...used with gases in groups Group A propane Group B ethylene Group C hydrogen Having a temperature classification of T1 450oC T2 300oC T3 200oC T4 135oC T5 100oC At an ambient temperature between 20 and...

Page 7: ...intrinsic safety approval the sensor may be installed in Zone 0 or 1 BEKA Application Guide AG310 provides comprehensive information on the design installation and maintenance of Extra low voltage dc...

Page 8: ...Zener barrier or galvanic isolator is required thus reducing complexity and cost There are four requirements when designing a BA474ND loop 1 The output voltage of the supply powering the transmitter...

Page 9: ...terminal should be connected to a local earth The BA474ND enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries The BA474ND liquid crystal...

Page 10: ...lly safe and non intrinsically safe terminals within the transmitter terminal enclosure Conductors of intrinsically safe circuits and non intrinsically safe circuits should not be contained in the sam...

Page 11: ...ected by an access code the first parameter InPut will be displayed If the transmitter is protected by an access code CodE will be displayed first Pressing P will allow the four digit security code to...

Page 12: ...ts low or high display resolution See section 7 2 4 Transmitter Summary display of function FAuLt Sensor fault analogue indication Selects 1 of 3 under over range output currents to indicate that a se...

Page 13: ...rmocouple has been selected press E to enter the selection and return to the t tYPE prompt in the configuration menu 7 2 3 Units of digital display dEG The transmitter digital display may be in one of...

Page 14: ...ss P which will display the ZEro function in the sub menu pressing P again will reveal the existing transmitter input at which the transmitter output current is 4mA Input is shown in units which depen...

Page 15: ...return control to one of the digits 7 2 9 Access code for configuration menu CodE Access to the configuration menu may be protected by a four digit security code which must be entered to gain access N...

Page 16: ...oned using either the or button Pressing the P button again will return control to one of the digits 7 2 13 Higher input display in Hi This function which only appears in the menu when the transmitter...

Page 17: ...15...

Page 18: ...16...

Page 19: ...17...

Page 20: ...on site Function Factory default Transmitter input InPut 3 wire RTD Sensor type t tYPE Pt100 Units of digital display dEG C Display resolution rESn Low Sensor fault FAuLt Off 4 20mA output CAL 0 0 to...

Page 21: ...r the function which enables the type of resistance thermometer to be selected The transmitter will display the existing type of resistance thermometer using the or button select 100r which is the req...

Page 22: ...P to enter the bArLo sub function which will reveal the existing digital display at which the bargraph starts Set the display to 0100 0 using the or button to adjust the flashing digit and the P butto...

Page 23: ...raph flashing and 4 20mA fixed at 3 6 3 8 or 21 0mA Sensor fault detection has been activated Sensor and input wiring 9 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENA...

Page 24: ...Scale and tag marking BA474ND indicating temperature transmitters are fitted with a blank escutcheon around the liquid crystal display If specified when the transmitter is ordered this can be supplie...

Page 25: ...he outputs are polarised and current will only flow in one direction Terminals 8 and 10 should be connected to the positive side of the supply Ron 8ohms 1 2V Roff greater than 180k Note Because of the...

Page 26: ...functions Display Description of function ALr1 Alarm 1 ALr2 Alarm 2 The two functions each contain seven identical sub functions one set for configuration alarm 1 and the other for configuration alar...

Page 27: ...25...

Page 28: ...reveal the current setting The function may be changed by pressing the or button pressing the E button will enter the setting and return the display to the Hi Lo prompt in the alarm menu 10 4 8 Alarm...

Page 29: ...xists the alarm will be reactivated 10 4 12 Access Setpoint ACSP This function controls a separate menu that provides direct access to the alarm setpoints when the BA474ND transmitter is in the operat...

Page 30: ...to be displayed Pressing the or button will toggle between the two alarm setpoint prompts SP1 and SP2 If an incorrect security code is entered or a button is not pressed within ten seconds the transm...

Page 31: ...nput input terminals 1 2 3 4 is galvanically isolated and intrinsically safe Ex iaD When the transmitter is installed in a Zone 22 dust hazardous area this allows the transmitter sensor input terminal...

Page 32: ...d and that it is free from foreign bodies Use as a Ex nA Ex tD instrument with an intrinsically safe Ex ia sensor input Transmitter in Zone 22 sensor in Zone 20 or 21 Maintenance may only be performed...

Page 33: ...x gas and dust certification of the transmitter are identical to the ATEX certifications described in the main section and in Appendix 1 of this instruction manual Like the ATEX certificate the IECEx...

Reviews: