BEKA BA405C Manual Download Page 4

4

3.3

Safety parameters

The BA405C EC-Type Examination Certificate
specifies the maximum input safety parameters for
the two 4/20mA terminals 1 and 3, and the
equivalent internal capacitance and inductance
that appears between the terminals.  Using the
entity concept and these safety parameters,
suitable Zener barriers or galvanic isolators may
be selected and the maximum permissable cable
parameters calculated.

The following figures are reproduced from the
ATEX certificate ITS03ATEX21103

Terminals 1 and 3:

(4/20mA output terminals)

Basic BA405C set point station without
optional loop powered display backlight.

Maximum input safety parameters

Ui

=

   30V dc

Ii

=

 200mA dc

Pi

=

0.85W

Equivalent capacitance and inductance

Ci

=

   40nF

Li

=

0.01mH

With loop powered display backlight
Terminals 1 and 13

(3 and 12 connected in series)

Maximum input safety parameters

Ui

=

   30V dc

Ii

=

 200mA dc

Pi

=

0.85W

Equivalent capacitance and inductance

Ci

=

   40nF

Li

=

0.03mH

Separately powered display backlight
Terminals 12 and 13

Maximum input safety parameters

Ui

=

   28V dc

Ii

=

 159mA dc

Pi

=

0.8W

Equivalent capacitance and inductance

Ci

=

   30nF

Li

=

0.01mH

3.4  Zones, Gas Groups and T rating

The BA405C and both the optional display
backlights have been certified as Group II category
1G apparatus, EEx ia IIC T5.   When powered via
a compatable Zener barrier or galvanic isolator the
BA405C manual set point station may be installed
in:

Zone 

0

explosive gas air mixture
continuously present.

Zone 1

explosive gas air mixture likely
to occur in normal operation.

Zone 2

explosive gas air mixture not

likely to occur, and if it does will

only exist for a short time.

Be used with gases in groups:

Group

A

propane

Group

B

ethylene

Group

C

hydrogen

Having a temperature classification of:

T1

450°C

T2

300°C

T3

200°C

T4

135°C

T5

100°C

WARNING installation in Zone 0

When installed in a Zone 0 potentially
explosive atmosphere requiring apparatus
of Category 1G, the set point station shall be
installed such that even in the event of rare
incidents, an ignition source due to impact
or friction between the aluminium enclosure
at the rear of the instrument mounting panel
and iron/steel is excluded.

3.5

Certification label information

The ATEX certification information is shown on a
label fitted in a recess on the top outer surface of
the enclosure.

BA405C ATEX certification label

Summary of Contents for BA405C

Page 1: ...BA405C intrinsically safe 2 wire 4 20mA manual set point station issue 6 Issue 6 17th November 2009 ...

Page 2: ...n 5 1 Location 5 2 Installation procedure 5 3 EMC 6 Calibration 6 1 Internal display 6 1 1 Zero adjustment 6 1 2 Span adjustment 6 1 3 Decimal point 6 1 4 Reverse action 6 1 5 Calibration example 6 1 6 Over under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessories 8 ...

Page 3: ...hanges in the supply voltage Caution The 4 20mA output should not be used for critical safety applications The 3 digit internal indicator can easily be calibrated on site to show the loop current in engineering units For example in an application where the BA405C is being used to adjust the set point of a speed controller the internal indicator may be calibrated to display the requested speed in R...

Page 4: ...alent capacitance and inductance Ci 30nF Li 0 01mH 3 4 Zones Gas Groups and T rating The BA405C and both the optional display backlights have been certified as Group II category 1G apparatus EEx ia IIC T5 When powered via a compatable Zener barrier or galvanic isolator the BA405C manual set point station may be installed in Zone 0 explosive gas air mixture continuously present Zone 1 explosive gas...

Page 5: ...ish that the maximum voltage drop caused by the manual set point station both Zener barriers the load and cable resistance is always less than the minimum supply voltage Fig 2 Typical application using barriers In this example Minimum operating voltage of BA405C 6 1V Maximum voltage drop caused by 28V 6 8V 93mA 0 65W Zener barrier 340Ω end to end resistance x 20mA Maximum voltage drop caused by 1 ...

Page 6: ... 30nF Li 0 01mH Any Zener barrier or isolator certified EEx ia IIC by an EEC approved body which has output parameters equal to or less than the maximum input parameters specified above may be used Most installations would use a 28V 93mA 0 65W 28V 300Ω device as shown in Fig 4 The display brilliance depends upon the current flowing through the backlight which is determined by the supply voltage an...

Page 7: ...lease refer to BEKA associates if high vibration is anticipated Fig 6 shows the enclosure dimensions and the recommended panel cut out sizes 5 2 Installation Procedure a Insert the BA405C set point station into the panel aperture from the front Ensure that the gasket is correctly positioned under the bezel b Fix two panel mounting clips to opposite sides of the instrument and tighten until the ind...

Page 8: ...ed between 1000 and 1000 The zero potentiometer has two ranges 0 to 500 and 500 to 1000 Tthe polarity of the zero is defined by the position of the suppression elevation links Fig 9 shows the position of the zero links and zero potentiometer Suppression elevation links Elevation Positive zero 0 to 1000 or Suppression Negative zero 0 to 1000 Zero link 0 to 500 or 500 to 1000 6 1 2 Span adjustment S...

Page 9: ...A dummy decimal point is required between the least two significant digits therefore the decimal point link should be placed in the 00 0 position Step 5 Adjust the BA405C front panel control until the output current measured by external ammeter is 4 000mA The zero potentiometer at the rear of the BA405C should then be adjusted until the BA405C displays 25 0 Step 6 Adjust the BA405C front panel con...

Page 10: ...as clearance certificate is available If a BA405C fails after it has been functioning correctly the following procedure should be followed Symptom Cause Solution No loop Wiring or power Check wiring current supply fault and power supply Unstable Insufficient Check that voltage loop supply between terminals current voltage 1 3 is greater than 6 1 or 10V between terminals 1 13 if fitted with a loop ...

Page 11: ...to the shaft Loosen the collet by turning the brass split screwhead anti clockwise and then carefully pull the control knob from the shaft c Pull the electronic assembly from the rear of the enclosure d Remove the blank scale card s and mark with the required legend Replace scale card s taking care to align them within the front panel window e Slide the electronic assembly into the rear of the enc...

Page 12: ...es Intrinsic Safety Division 1 or 2 Class I Group A B Group C Group D Zone 0 1 or 2 Class 1 Group IIC Group IIB Group IIA The FM entity parameters are similar to the ATEX parameters The intrinsically safe systems shown in this manual may therefore be used for installations in the USA providing the Zener barriers or galvanic isolators are FM Approved All installations must comply with BEKA associat...

Page 13: ...13 ...

Page 14: ...14 ...

Page 15: ...15 ...

Page 16: ...16 ...