![BEKA BA307E-SS Manual Download Page 24](http://html1.mh-extra.com/html/beka/ba307e-ss/ba307e-ss_manual_2723882024.webp)
9.3.4 Alarm enable: ‘EnbL’
This function allows each alarm to be enabled or
disabled without altering any of the alarm parameters.
To enable or disable the alarm select 'EnbL' from the
alarm menu and press
P
which will reveal the current
setting ‘on’ or ‘oFF’. The function can be changed by
pressing the
▲
or
▼
button followed by the
E
button
to return to the alarm menu.
9.3.5 Setpoint adjustment: ‘SP1’ and ‘SP2’
The setpoint of each alarm may be positioned
anywhere in the numerical display of the indicator
providing that this corresponds to an input current
between 3.8 and 20.2mA. e.g. If the indicator has
been calibrated to display 0 with 4mA input and 10000
with 20mA input, the two alarm setpoints may be
positioned anywhere between -125 and 10125.
To adjust the setpoint select 'SP1' or 'SP2' from the
alarm configuration menu and press
P
which will
reveal the existing alarm setpoint. The flashing digit
of the setpoint can be adjusted using the
▲
and
▼
push buttons, and the
P
button to move control to the
next digit. When the required setpoint has been
entered press
E
to return to the alarm configuration
menu.
The alarm setpoints may also be adjusted when the
indicator is in the display mode, see section 9.3.12.
9.3.6 Alarm function: ‘Hi.Lo’
Each alarm can be independently conditioned as a
high alarm or as a low alarm. To check or change the
alarm function select 'Hi.Lo' from the alarm menu and
press
P
to reveal the current setting. The function can
be changed by pressing the
▲
or
▼
button followed
by the
E
button to return to the alarm menu.
9.3.7 Alarm output status: ‘no.nC’
Configures the solid state alarm output to be open ‘no’
or to be closed ‘nC’ in the non-alarm condition. When
deciding which is required, care should be taken to
ensure that the alarm output is fail safe as illustrated
in Fig 13.
‘no’ Alarm output open in non-alarm condition
‘nC’ Alarm output closed in non-alarm condition
CAUTION
When the 4/20mA supply is removed from
the loop powered indicator, both alarm
outputs will open irrespective of
conditioning. Therefore for fail safe
operation both alarm outputs should be
conditioned to be open in the alarm
condition ‘nC’.
To check or change the alarm output status, select
'no.nC' from the alarm configuration menu and
press
P
to reveal the setting. The function may be
changed by pressing the
▲
or
▼
button followed
by the
E
button to return to the alarm configuration
menu.
9.3.8 Hysteresis: HStr
Hysteresis is shown in the units that the indicator
has been calibrated to display.
To adjust the hysteresis select 'HStr' from the
alarm menu and press
P
which will reveal the
existing figure. The flashing digit can be adjusted
using the
▲
and
▼
push buttons, and the
P
button
will move control to the next digit. When the
required hystersis has been entered press
E
to
return to the alarm configuration menu.
e.g. An indicator calibrated to display 0 to 10000,
with a high alarm set at 9000 and hysteresis of 200
will perform as follows:
The high alarm will be activated when
increasing indicator display equals 9000, but
will not reset until the indicator display falls
below 8800.
9.3.9 Alarm delay: dELA
This function delays activation of the alarm output
for an adjustable time following the alarm condition
occurring. The delay can be set in 1 second
increments between 0 and 3600 seconds. If a
delay is not required zero should be entered. To
adjust the delay select 'dELA' from the alarm
configuration menu and press
P
which will reveal
the existing delay. The flashing digit of the delay
can be adjusted using the
▲
and
▼
push buttons,
and the
P
button to move control to the other digits.
When the required delay has been entered press
E
to return to the alarm menu.
e.g. An indicator with a high alarm set at 9000 and
an alarm delay of 30 seconds will perform as
follows:
The alarm annunciator will start to flash when an
increasing indicator display equals 9000, but the
alarm output will not be activated until the alarm
condition has existed continuously for 30 seconds.
When the alarm output is activated, the alarm
annunciator will stop flashing and become
permanently activated.
If the ‘FLSH’ function, which flashes the indicator
display when an alarm occurs, has been enabled,
it will not start to function until the alarm output is
activated.
See section 9.3.11
24