DESCRIPTION

The   BA304NE   and   BA324NE   are   field   mounting,   Ex  nA
and Ex tc certified digital indicators that display the current
flowing  in  a 4/20mA  loop  in  engineering  units. They are
loop powered but only introduce a 1.2V drop into the loop.

The two models are electrically similar, but have different
size displays.

Model

Display

BA304NE 

4 digits 34mm high

BA324NE

5 digits 29mm high and 
31 segment bargraph.

This abbreviated instruction sheet is intended to assist with
installation   and   commissioning,   a   comprehensive
instruction   manual   describing   safety   certification,   system
design  and   calibration   is   available   from   the   BEKA  sales
office or may be downloaded from our website.

Both models have ATEX and IECEx certification permitting
installation   in   Zone   2   flammable   gas   and   Zone   22
combustible dust atmospheres without the need for Zener
barriers or galvanic isolators. The certification label, which
is located on the top of the instrument enclosure, shows
the certificate numbers and the certification codes. Copies
of certificates may be downloaded from our website.

All models have gas and dust certification.

2.

INSTALLATION

The BA304NE and BA324NE indicators have robust IP66
glass reinforced polyester (GRP) enclosures incorporating
an   armoured   glass   window   and   stainless   steel   fittings.
They are suitable for exterior mounting in industrial Zone 2
or Zone 22 environments.

They   are   surface   mounting,   but   may   be   pipe   mounted
using an accessory kits.

Fig 1 shows the installation procedure.

Fig 1 Installation procedure

Fig 2 Dimensions and terminal connections

The indicator’s earth terminal is connected to the carbon
loaded GRP enclosure. If this enclosure is not bolted to an
earthed   post   or   structure,   the   earth   terminal   should   be
connected to the plant potential equalising conductor.

A bonding plate is provided to ensure electrical continuity
between the three conduit / cable entries. 

Terminals 8, 9, 10 & 11 are only fitted when the indicator
includes optional alarms.  See full manual for details.

Terminals 12, 13 & 14 are only fitted when the indicator
includes an optional backlight.  See full manual for details.

EMC

For   specified   immunity   all   wiring   should   be   in   screened
twisted pairs, with the screens earthed in the safe area.

Fig 3 Typical measurement loop

Units of measurement & tag number

Both   indicators   have   an   escutcheon   around   the   liquid
crystal   display   which   can   be   printed   with   any   units   of
measurement   and   tag   information   specified   when   the
indicator was ordered. If no information is supplied a blank
escutcheon will be fitted but legends may be added on-site
via an embossed strip, dry transfer or a permanent marker.
Printed   escutcheons   are   available   from   BEKA   as   an
accessory   which   should   be   fitted   on   top   of   the   blank
escutcheon. Do not remove the blank escutcheon.

To   gain   access   to   the   escutcheon   remove   the   terminal
cover by unscrewing the two 'A' screws which will reveal
two concealed 'D' screws. If the instrument is fitted with an
external keypad, also unscrew the two 'C' screws securing
the   keypad   and   unplug   the   five   way   connector.     Finally
unscrew all four 'D' screws and carefully lift off the front of
the instrument.

3.

OPERATION

The indicators are controlled and configured via four push
buttons located behind the instrument control cover, or via
an optional keypad on the outside of the control cover. In
the   display  mode   i.e.  when   the  indicator  is  displaying   a
process   variable,  these   push   buttons  have   the   following
functions:

P

While   this   button   is   pushed   the   indicator   will
display   the   input   current   in   mA,   or   as   a
percentage   of   the   instrument   span   depending
upon   how   the   indicator   has   been   condtioned.
When the button is released the normal display in
engineering units will return. The function of this
push button is modified when optional alarms are
fitted to the indicator.

While   this   button   is   pushed   the   indicator   will
display   the   numerical   value   and   analogue
bargraph*   the   indicator   has   been   calibrated   to
display with 4mA input. When released the normal
display in engineering units will return.

While   this   button   is   pushed   the   indicator   will
display   the   numerical   value   and   analogue
bargraph*   the   indicator   has   been   calibrated   to
display   with   20mA   input.   When   released   the
normal display in engineering units will return.

E

No function in the display mode unless the tare
function is being used.

P

 + 

Indicator   displays   firmware   number   followed   by
version.

P

 + 

When   optional   alarms   are   fitted   provides   direct
access to the alarm setpoints if the ‘ACSP’ access
setpoints   in   display   mode   function   has   been
enabled.

P

 + 

E

Provides   access   to   the   configuration   menu   via
optional security code.

* Only the BA324NE has a bargraph

Issue 2
10th March 2014

BEKA associates Ltd

Old Charlton Rd, Hitchin, Hertfordshire,

SG5 2DA, UK     Tel: +44(0)1462 438301     Fax: +44(0)1462 453971
e-mail: 

[email protected]

                                   web: 

www.beka.co.uk

Abbreviated Instruction for

BA304NE and BA324NE Ex nA and Ex tc

field mounting loop powered indicators

The   BA304NE   &   BA324NE   are   CE   marked   to   show
compliance with the European Explosive Atmospheres
Directive   94/9/EC   and   the   European   EMC   Directive
2004/108/EC