Power  Supply    ..........................................................................................................  12÷24VDC    ±  10%
Power demand ................................................................. 90 mA in operating, 160 mA in alarm Max @ 13,8 V
Main  Alarm  Relay  Contact Range   ..........................................................................  5A  30Vdc  resistive SELV

OXYGEN
For  Oxygen  ..............................................................................................................  Optical 

  fluoresence

Gas  Detection:    ......................................................................................................................  Oxygen
Sensitive  element  working  range,      .....................................................................................  0  -  25  %  di  O

2

Detection  mode Selectable by switch  ............................................... 18%  ÷  20,8%  O

2

 , or   20,8%  ÷ 22,5%  O

2

Detector  accuracy  .....................................................................................................................  1%  FS
Long  term  shift  in  clean  air    ...........................................................................................................  <  3%

CARBON DIOXIDE

For 

Carbon  dioxide  ...................................................................................................  Infrared  technology

Gas  Detection:    ...................................................................................................

  Carbon  dioxide  (CO

2

)

Detection  mode Selectable  by  switch  ....................................................................... 

5%,  10%,  15%  or  20%

Detector  accuracy  .....................................................................................................................  1%  FS
Long  term  shift  in  clean  air    ...........................................................................................................  <  3%
Response Time  ............................................................................................................................ <10”Analog
Output  signal...........................................................................................

......  4÷20  mA  standard  tolerance

Auto  zero  procedure    ............................................................................  Included  in  the  software algorithms

Warm-up  time  ...................................................................................................................  1,30  minutes
Functioning  humidity    .............................................................................................  0-90%  non  condensed
Functioning  temperature    ................................................................................................  -10°C  to  +50°C

For Oxygen Control units usable ........................................ BX444-Mc, BX449F, GS300-Mc, BX316xp, BX308xp

For 

Carbon dioxide Control units usable ............................ Not connected to any control unit. It is autonomous

Max.  distance  between  probe  and  unit    ..........................................................................................  100  m
Cable  diameter  for  connecting  probe    ..............................................................................................  1  mm
Connection: The cable of connection of the probe must not be installed together with the power cables.
Otherwise, make sure to use a shielded cable
Probe’s body material   ............................................................................................................. Alluminium
External  degree  of  protection    ........................................................................................................  IP66
Size    .................................................................................................................................  100x100x60

CHECK the integrity of the unit after having removed it from the box.
Check that the data written on  the box correspond to the  type of gas  used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper, and as a result
of which BEINAT S.r.l. therefore disclaims any responsibility for possible damages caused to people,
animals or objects.
TERMS and  EXPECTATIONS:  The  installation  of  the  SG850  Probe,  its  ordinary  and  extraordinary
maintenance, every six months, and its out of service removal at the end of the functional life guaranteed
by the manufacturer, must be carried out by authorized or specialized personnel.
Do not allow it to become wet.
The control unit can be seriously  damaged as it is not waterproof either when  immersed in  water or
exposed to high levels of humidity.
Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.
Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the control unit could work poorly.
Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.

Code

 

         Type of Gas

                      Sensor

        Working range                   Temperature

SG850 O

2

Oxigen

optical 

  fluoresence

>  E

XCESS

   

OR

    <D

EFICIENCY

-30+50°C

SG800 CO

2

Carbon dioxide

Infrared technology 5%, 10%, 15% or 20%

         -10+50°C

Technical Features  SG800

Technical  Specifications

Precautions

Summary of Contents for SG850

Page 1: ...AT industrial control unit or in stand alone mode detects the presence of Oxygen Carbon Dioxide SG850 O2 FOROXYGEN DETECTION This sensor through an optical fluorescence technology based sensor detects the presence of Oxygen O2 With this probe it is possible to 1 SELECT THE ALARM INTERVENTION FOR OXYGEN EXCESS OR DEFICIENCY 2 SELECT THE POSITIVE SAFETY OF THE RELAY SG850 CO2 FOR CARBON DIOXIDE DETE...

Page 2: ... 100x100x60 CHECK the integrity of the unit after having removed it from the box Check that the data written on the box correspond to the type of gas used When doing the electrical connections follow the drawing closely Any use of the detector for purposes other than the intended one is considered improper and as a result of which BEINAT S r l therefore disclaims any responsibility for possible da...

Page 3: ...dition is reached At least once a year make a more accurate check by a specialist technician Disabling the detector must be carried out by qualified personnel Side view 60 mm Compatible control units Only Oxygen CONTROL UNITS MOUNTING PROBES Max DEGREE PRE ALARMS POSITIVE OPERATING protec alarms safety range GS300 Mc unit 1 zone Wall cabinet 3 IP44 2 1 YES NO BX444 MC unit 1 zone Wall cabinet 4 IP...

Page 4: ...oor Light medium gas volatile The probe should not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans Page 4 0 18 5 19 5 20 9 22 5 23 5 25 0 vol 0 4 15 8 16 5 17 4 18 4 19 ...

Page 5: ...age at the terminals 1 2 It must be higher than 11Vdc and lesser than 25Vdc Check the voltage at the terminals 2 3 It must be from a minimum of 0 8 Vdc to a maximum of 1 1 Vdc If other problems arise the Distributor of BEINAT S r l should be contacted directly Linear Otput 4 20 mA 3 2 1 R 0 1 3 2 1 1 VDC Voltmeter Power Supply 12 24 V WARNING These measurement should be performed in clean air More...

Page 6: ... Fault Operating LEDs IMPOSTAZIONI ALLARMI MICRO INTERRUTTORI n 2 n 3 5 OFF OFF 10 OFF ON 15 ON OFF 20 ON ON SWITCH 1 Positive safety Position ON Positive security enabled Position OFF Positive security disable WARNING Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the s...

Page 7: ...nder tap 3 Do not turn any lights on or off do not turn on any electrical device or appliance 4 Open windows and doors in order to increase ventilation If the alarm stops its cause must be found and the relevant consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department ...

Page 8: ...ts in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste handing of this product The recycling of materials will help to conserve natural reso...