Page 2
Power Supply .......................................................................................................... 12÷24VDC ± 10%
Power demand ................................................................. 90 mA in operating, 160 mA in alarm Max @ 13,8 V
Main Alarm Relay Contact Range .......................................................................... 5A 30Vdc resistive SELV
OXYGEN
For Oxygen .............................................................................................................. Optical
fluoresence
Gas Detection: ...................................................................................................................... Oxygen
Sensitive element working range, ..................................................................................... 0 - 25 % di O
2
Detection mode Selectable by switch ............................................... 18% ÷ 20,8% O
2
, or 20,8% ÷ 22,5% O
2
Detector accuracy ..................................................................................................................... 1% FS
Long term shift in clean air ........................................................................................................... < 3%
CARBON DIOXIDE
For
Carbon dioxide ................................................................................................... Infrared technology
Gas Detection: ...................................................................................................
Carbon dioxide (CO
2
)
Detection mode Selectable by switch .......................................................................
5%, 10%, 15% or 20%
Detector accuracy ..................................................................................................................... 1% FS
Long term shift in clean air ........................................................................................................... < 3%
Response Time ............................................................................................................................ <10”Analog
Output signal...........................................................................................
...... 4÷20 mA standard tolerance
Auto zero procedure ............................................................................ Included in the software algorithms
Warm-up time ................................................................................................................... 1,30 minutes
Functioning humidity ............................................................................................. 0-90% non condensed
Functioning temperature ................................................................................................ -10°C to +50°C
For Oxygen Control units usable ........................................ BX444-Mc, BX449F, GS300-Mc, BX316xp, BX308xp
For
Carbon dioxide Control units usable ............................ Not connected to any control unit. It is autonomous
Max. distance between probe and unit .......................................................................................... 100 m
Cable diameter for connecting probe .............................................................................................. 1 mm
Connection: The cable of connection of the probe must not be installed together with the power cables.
Otherwise, make sure to use a shielded cable
Probe’s body material ............................................................................................................. Alluminium
External degree of protection ........................................................................................................ IP66
Size ................................................................................................................................. 100x100x60
CHECK the integrity of the unit after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper, and as a result
of which BEINAT S.r.l. therefore disclaims any responsibility for possible damages caused to people,
animals or objects.
TERMS and EXPECTATIONS: The installation of the SG850 Probe, its ordinary and extraordinary
maintenance, every six months, and its out of service removal at the end of the functional life guaranteed
by the manufacturer, must be carried out by authorized or specialized personnel.
Do not allow it to become wet.
The control unit can be seriously damaged as it is not waterproof either when immersed in water or
exposed to high levels of humidity.
Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.
Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the control unit could work poorly.
Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.
Code
Type of Gas
Sensor
Working range Temperature
SG850 O
2
Oxigen
optical
fluoresence
> E
XCESS
OR
<D
EFICIENCY
-30+50°C
SG800 CO
2
Carbon dioxide
Infrared technology 5%, 10%, 15% or 20%
-10+50°C
Technical Features SG800
Technical Specifications
Precautions