The position of the probe is a crucial factor for a gas detection unit correct functioning.
In order to obtain the maximum results from an appliance and minimize the probabilities of false alarms, we recommend
to follow this diagram and to keep in mind the following general rules.
The remote probe must be located at different heights, according to the type of gas.
These heights are:

- 30 cm from the lowest point of the floor in order to detect

heavy gases (L.P.G. etc.)

- 30 cm from the highest point of the ceiling in order to detect

light gases (Methane, etc.)

The probe should not be placed near the appliances to be controlled (boilers, burners, industrial kitchens, etc.) but
on the opposite wall.
The probe should not be affected by smoke, vapour, etc. as they could distort their measurement. It must be placed
away from sources of heat, suction fans, ventilation fans.

30 cm. 

Light  Gases

30  cm.

  Heavy  Gases

NO !

yes

NO !

Positioning  of the Probe

Detection  Diagrams Data

0       4%       8%      12%       16%       20%

0

  

  

4

  

5

  

  

1

0

  

  

  

 1

5

  

  

 2

0

 

  7,2

 

  10,4

 

  13,6

 

  16,8

 

  20

    mA

L E L

Fau lt  Zone

L in ea r  +/ -5 %

Explosive Detection Diagram

ppm

0         50      100      150       200      250      300

 

  6,7

0

  

  

  

4

  

5

  

  

 1

0

  

  

  

 1

5

  

  

  

2

0

 

  7,2

 

  20

m A

 

  9,3

 

  12

 

  14,6

 

  17,3

L in ea r  +/ -5 %

Fau lt  Zone

Diagram of Toxic Gas Detection

Summary of Contents for SG500

Page 1: ...70 Compliant EN 60079 29 1 Installation EN 60079 29 2 Reports issued by TUV Italia Channel Beinat gas solutions Electric connections also available on Conventional Gas Sensor SG500 V 3 The SG500is born from the elegance and prestige that has always distinguished BEINAT S r l and from the home fitness concept The probe is a Catalytic gas detection unit with IP30 protection that together with one of...

Page 2: ...ge of measurement 0 100 of L E L Detector range of measurement 0 20 of L E L Detection Gas Methane LPG Output 4mA 20mA standard tolerance Accuracy 1 Long term shift in clean air 3 LELWarm up time 1 5 minutes Control units that can be used BX444 Mc BX449F GS100M BX280 BX180 GS300Mc BX316xp BX308xp Functioning Humidity 0 90 non condensed Functioning Temperature 10 C to 50 C Max distance between prob...

Page 3: ...unit 1 zone Wall cabinet 4 IP44 2 1 YES NO BX150 unit 1 zone Panel 1 IP42 1 1 YES NO BX180 unit 1 zone Omega bar DIN 1 IP20 1 1 YES NO BX280 unit 1 zone Omega bar DIN 2 IP20 1 1 YES NO BX449F unit 1 zone Omega bar DIN 4 IP20 1 1 YES NO BX308xp unit 1 zone Omega bar DIN 8 IP20 1 1 YES YES BX308xp Box unit 1 zone Wall 8 IP65 1 1 YES YES BX316xp unit 2 zones Barra Omega 16 IP20 1 2 YES YES BX316xp Bo...

Page 4: ...point of the ceiling in order to detect light gases Methane etc The probe should not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans 30 cm Light Gases 30 cm Heavy Gases ...

Page 5: ...is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables Electrical connections Sensor Gas On R 1 2 3 R 3 2 1 Power Supply 12 24 V Linear Output 4 20 mA ...

Page 6: ... technician and or the Distributor of BEINAT S r l should be contacted directly The installation of the SG500 probe its ordinary and extraordinary maintenance and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized or specialized personnel The general test should be performed by issuing gas from a pre calibrated aerosol Acco...

Page 7: ...consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department distributors etc IMPORTANT The operation test should not be carried out with the gas tap as this does not guarantee a sufficient concentration to activate the general alarm Warning If you have the following sympt...

Page 8: ...all be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable...

Reviews: