Technical Specifications

Operating specifications of the gas sensors

The  installation  of  the  GS920  detector,  its  ordinary  and  extraordinary  maintenance,  and  its  out  of
service removal at the end of the functional life guaranteed by the manufacturer, must be carried out
by  authorized  and/or  specialized  personnel.
The  CATALYTIC  technology  sensor  duration  is  guaranteed  for  6  years  (in  clean  air).  The  detector’s
functioning  temperature  ranges  from  -10°C  to  +  40°C.

WARNING!

The  CATALYTIC  probe  does  not  tolerate  a  gas  detection  exceeding  100%  of  L.E.L.,  with  consequent
natural  death  of  the  sensor.
Each  immediate  puff of  gas  that  exceeds  100%  of L.E.L.  takes  away  months  of  life  from  the  sensor.
The  detector  must  be  tested  by  simulating  the  presence  of  gas  by  issuing  it  from  a  pre-calibrated
testing  aerosol.
A  common  cigarette  lighter  near  the  sensor  does  not  guarantee  excellent  functioning.

Precautions

CHECK  the  integrity  of  the  probe  after  having  removed  it  from  the  box.
Check  that  the  data  written  on  the  box  correspond  to  the  type  of  gas  used.
When  doing  the  electrical  connections,  follow  the  drawing  closely.
Any  use  of  the  detector  for  purposes  other  than  the  intended  one  is  considered  improper,  and  as  a
result  of  which  BEINAT  S.r.l.    therefore  disclaims  any  responsibility  for  possible  damages  caused  to
people,  animals  or  objects.

INSTALLATION
When  performing  the  installation,  please  remind  that  if  you  pierce  the  GS920  container,  it  will  lose
its  properties  and  its  conformity  to  REGULATIONS.
TERMS and EXPECTATIONS: The installation of  the GS920 detector, its ordinary and extraordinary
maintenance,  and  its  out  of  service  removal  at  the  end  of  the  functional  life  guaranteed  by  the
manufacturer, must be carried out by authorized and/or  specialized personnel.
Do not allow it to become wet.
The  detector  can  be  seriously  damaged  when  immersed  in  water.  Remember  that  the  probe  has  an
IP30    protection  degree.
Do not drop it.
Heavy  knocks  or  falls  during  transportation  or  installation  can  damage  the  appliance.
Avoid abrupt temperature fluctuations.
Sudden  temperature  variations  can  cause  condensation  and  the  probe  could  work  poorly.
Cleaning
Never  clean  the  device  with  chemical  products.  If  necessary,  wash  with  a  moist  cloth.
Absolutely  avoid  using  any  cloth  dipped  in  thinners,  alcohol  and  chemical  detergents.

Mains power  ........................................................ 230VAC 50 Hz +/- 10% or using a 12VDC battery
Battery power  .......................................................................................... 12 VDC – 1.2 Ah +/- 10%
Current consumption  ................................................................................................ 3.6W @ 230V
Range of relay contact  switching  ....................................... 10A 250V resistive - 5A 30Vdc resistive
Battery  charger

 ........................................................................ Built in for a 1.2Ah 12VDC battery

Explosive gas sensor  ........................................................................................................ Catalytic
Explosive gas detector alarm threshold  ................................................................ At 10% of L.E.L.
Sensor’s  faults  detected  by  Fault  Circuit    ..................................  Interruption,  short  circuit,  or  wear
Detection capsule end-of-life warning  ....................................................................... After 6 years
Intrinsic safety control .......................................................................................................... Built in
Timed  or  continuous  functioning  solenoid  valve  selection    .......................................  Using  a  switch
Earthquake-proof sensor  ........................................................................ Three-axis accelerometer
Trigger sensitivity  .......................................................................... 6

th

 degree on the Mercalli scale

Audible and visual signal alarm by  ............................................................... LED diode and buzzer
Test phase duration  ..................................................................................................... 60 seconds
Functioning temperature  ....................................................................................... -10°C to +40°C
Functioning humidity  ............................................................................ 0÷90% RH non condensed
Electromagnetic compatibility CE Reference Norms  ......................................................... EN 50270
External degree of protection  ................................................................................................. IP42
Mounting  .................................................................... External wall mount, or embedded box 503
Body material  ............................................................................................... ABS self-extinguishing
Dimensions  ................................................................................................................. 115x150x52
Warranty  ............................................................................................................................ 3 years

Summary of Contents for GS920

Page 1: ...an activate solenoid valves sirens and any other alarm signal device The micro switch makes it possible to select the relay impulse functioning to connect manual reset solenoid valves or the continuous functioning and to activate N C class A solenoid valves and sirens Another micro switch allows turning on off the Intrinsic Safety The power supply unit allows driving of a manual reset solenoid val...

Page 2: ...traordinary maintenance and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized and or specialized personnel Do not allow it to become wet The detector can be seriously damaged when immersed in water Remember that the probe has an IP30 protection degree Do not drop it Heavy knocks or falls during transportation or installati...

Page 3: ...er level at 10 of L E L 4 Micro switches Switch 1 Positioning the switch to ON Intrinsically safe operation the relay is excited at the end of the latency time and switches on each alarm Positioning the switch to OFF Normal operation the relay switches on each alarm Switch 2 Positioning the switch to ON the relay is set to impulse functioning Each pulse lasts about 30 seconds Positioning the switc...

Page 4: ...Pagina 4 34 mm 50 mm Embedded box 503 70 mm 105 mm 5 mm 115 mm 84 mm 115mm Dimensions ...

Page 5: ... its measurement It should be located away from sources of heat ventilators or fans It must not be installed on a wall in plasterworch It must be installed only on walls in masonry Once the device has been turned on the MAINS LED will start blinking for about 60 seconds after which it will remain ON Now the GS920 is ready for detection of explosive gas After 24 hours from installation begin the se...

Page 6: ...les cornices also unbraced parapets and architectural ornaments Some cracks in masonry C Waves on ponds water turbid with mud Small slides and caving in along sand or gravel banks Large bells ring Concrete irrigation ditches damaged Steering of motor cars affected Damage to masonry C partial collapse Some damage to masonry B none to masonry A Fall of stucco and some masonry walls Twisting fall of ...

Page 7: ...ndon the building and call the emergency services when outside fire department distributors etc If the device does not start up Check that the 230V power is correctly connected If the fault LED lights up If the YELLOW LED is remains ON check the detection capsule status It is probably faulty and has to be replaced Call an authorized technician If the detector is repeatedly issuing an alarm Check t...

Page 8: ...tion Scheme of GS920 Detector N C C NO N Ph 12 V 1 2 3 4 5 6 7 8 Without Intrinsic Safety With Intrinsic Safety Normally closed electrovalve 230VAC The Relay is free of voltage Range of relay contact 10A resistive The electrovalve is a N C Automatic or manual retrig Note To connect a N O Electrovalve swap the connections between pin 8 and 6 The Relay is free of voltage Range of relay contact 10A r...

Page 9: ... free of voltage Range of relay contact 10A resistive The drawn electrovalve is a Normally Open type with manual reset and with a power supply of 12V 600mA MAX The activation is impulsive Power Supply 230 V AC Normally open electrovalve 230V AC with intrinsic safety Ph N 1 2 3 4 5 6 7 8 The Relay is free of voltage Range of relay contact 10A resistive The drawn electrovalve is a N C type with manu...

Page 10: ...open electrovalve 230V AC without intrinsic safety The Relay is free of voltage Range of relay contact 10A resistive The drawn electrovalve is a Normally Open type with manual reset and with a power supply of 12V 600mA MAX The activation is impulsive Power Supply 230 V AC Electricalconnections ...

Page 11: ...Page 11 Note ...

Page 12: ... 3 years from manufacturing date in agreement with the following conditions The components acknowledged as faulty will be replaced free of charge excluding the replacement of plastic or aluminium cases bags packing batteries and technical reports The device must arrive free of shipment charges to BEINAT S r l Defects caused by unauthorized personnel tampering incorrect installation and negligence ...

Reviews: