background image

Page  4

Turn on and testing

30  cm
m a x

1-4  m

30  cm
m a x

1-4  m

N O !

N O !

Detector  Gas
METHANE

YES

Detector  Gas
LPG

Furthermore,  the  correct  electrical  connections  according  to  the  enclosed  drawings,  complying  with
instructions  and  Regulations  in  force,  and  the  use  of  the  safety  fuse,  are  recommended.
Indeed, the  most  essential factor for the proper functioning  of the GS911K  is its  correct installation.
By  following  the  instructions  in  this  paragraph  high  precision  can  be  obtained  together  with  the
absence  of  false  alarms.

Once the device has been turned on, the MAINS LED lights up, and the GS911K is ready for detection
after  60  seconds.
Press  the  button  near  the  detection  capsule  to  simulate  the  presence  of  gas.

  The  ALARM  LED  lights  up,  and  the  relay  shifts  its  functioning  mode  after  one  second.
After the alarm, the LED will turn off, the buzzer will stop, and the connected appliances will be turned
off.

To  complete  the  general  test,  issue  gas  from  a  pre-calibrated  aerosol  within  20%  of  L.E.L.  Testing
using  a  common  cigarette  lighter  could  damage  the  sensor.

Installation measures and positioning

The  position  of  the  detector  is  a  crucial  factor  for  its  correct  functioning  during  gas  detection.
In  order  to  obtain  the  maximum  results  from  a  device  and  minimize  the  probability  of  false  alarms,
it  is  recommended  to  follow  this  scheme  and  keep  in  mind  the  following  general  regulations.

The  detector  must  be  located  at  different  heights,  according  to  the  type  of  gas.  These  heights  are:

-  30  cm  from  the  lowest  point  of  the  floor  in  order  to  detect

heavy gases, LPG, etc.

-  30  cm  from  the  highest  point  of  the  ceiling  in  order  to  detect

light gases, Methane

- The detector should not be placed near the appliances to be controlled (boilers, burners, industrial
kitchens,  etc.)  but  on  the  opposite  wall.

- The detector should not be affected by smoke, vapour, etc. as they could distort its measurement.
It  should  be  located  away  from  sources  of  heat,  ventilators  or  fans.

Summary of Contents for GS911K

Page 1: ...l reset solenoid valves or the continuous functioning to activate class A solenoid valves and sirens The relay free of voltage allows installation of multiple detectors on a single solenoid valve ensuring control of multiple dangerous environments The detector is complete with a special circuit that controls the catalytic sensor s efficiency level and signals any possible fault The external contai...

Page 2: ...inners alcohol and chemical detergents Power supply 230Vac 50 Hz 10 Power consumption 1W 230V Range of relay contact switching 10A 250V resistive 5A 30Vdc resistive Explosive gas sensor Catalytic Explosion Alarm Threshold At 10 of L E L Explosive gas detector alarm threshold Immediate Sensor s faults detected by Fault Circuit Interruption short circuit or wear Audible and visual signal alarm by LE...

Page 3: ...oles the relay will be set to impulse functioning That is when the alarm is triggered the relay will close the C and NA contacts for about 90 seconds and then will reopen them This is needed to prevent damaging some types of manual reset solenoid valve coils By opening the two poles the relay will be set to continuous functioning 5 Catalytic sensor for Methane or LPG explosive gas detection 6 TEST...

Page 4: ... appliances will be turned off To complete the general test issue gas from a pre calibrated aerosol within 20 of L E L Testing using a common cigarette lighter could damage the sensor Installation measuresandpositioning The position of the detector is a crucial factor for its correct functioning during gas detection In order to obtain the maximum results from a device and minimize the probability ...

Page 5: ...e alarm signal and the FAULT indicator light turn on together proceed as in the previous paragraph If the detector is issuing an alarm and does not shut off the devices connected to it Check that the wiring is correct and that the jumper that carries power to the relay has been set properly All relays are free from electrical power Check the drawing of the connections WARNING Actions to be taken i...

Page 6: ...N C C NO 1 2 3 4 5 Electricalconnections WARNING Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables Jumper for Relay working Mode 1 With the Jumper opened the relay works in continuos Mode 2 With the Jumper clos...

Page 7: ...oltage One detector with 230V normally open valve WARNING All relays are free of voltage One or more detectors with 230V normally closed valve N Power Supply 230V ca Ph Electrovalve N C C NO 1 2 3 4 5 Ph N Power Supply 230V ca 1 2 3 4 5 1 2 3 4 5 Ph N Power Supply 230V ca 1 2 3 4 5 1 2 3 4 5 ...

Page 8: ... 3 years from manufacturing date in agreement with the following conditions The components acknowledged as faulty will be replaced free of charge excluding the replacement of plastic or aluminium cases bags packing batteries and technical reports The device must arrive free of shipment charges to BEINAT S r l Defects caused by unauthorized personnel tampering incorrect installation and negligence ...

Reviews: