background image

Page  8

Components and Commands continue

Description of Micro-switches

Installing, uninstalling or disabling probe

Through  the  Micro  switches  (see  drawing  below)  on  the  control  unit,  you  can  to  activate  or  to    deactivate    3
Zo nes 
.
You  can  connect  3  probes  to  the  GS300-Mc.  The  control  unit  is  tested  with  the  probes  connected
In  some  installations,  you may  need  only  one  probe.  In  this  case  we  will  proceed  to  disable  a  probe,  to  do  this
select  the  switch  of  the  probe  (zone)  concerned.
These  micro-switches  are  also  used  to  disable  one  or  all  probes  in  case  of  failure

N.B.  The  microswitches  are  also  used  for  switching  off  in  case  of  failure

A  row  of  LEDs  numbered  from 

1  to  3 

and  called  PROBES  has  been  fitted  on  the  GS300-Mc.  These  LEDs  are

lit  with  a  4  second  frequency  representing  the  connected  probes,  and  indicate  the  probe  being  read  on  the
display.

In  case  of  alarm:  The  LED  that  represents  the  probe  stops  for  about  15  seconds.  This  is  done  in  order  to
identify  the  relevant  zone  or  zones  easily.
The  gas  percentage  measured  by  the  probe  appears  on  the  display  and  is  maintained  for  15  seconds.  On  the
next  pass,  the  LED  (probe)  will  be  maintained  again  and  the  alarm  will  be  issued.
In case of fault:  The LED of the  relevant probe  starts blinking  and remains  lit. The  display will show the 

FAU

(Fault)  fixed  indication,  and  the  buzzer  will  issue  a  continuous  sound  until:
1)  The  repair  has  been  carried  out;
2)  The  relevant  probe  has  been  disabled  using  the  micro-switch.

Probe indication
Leds

  from  n°1  to  n°3

Zone 1        Zone 2        Zone  3

Micro-switch  (1)  to  enable  or  to  disable  the  probe.

Position ON enabled - In  position OFF  disabled

000

LEL
ppm

1    2    3

The simultaneous and prolonged pressure for 5 sec of the "TEST" and "RESET" buttons enables the test-on mode in
which the control unit does not switch the general alarm relay for a period of 15 minutes; Not even pressing the external
manual button.

A  further  keypress  in  the  same  mode  extends  the  time  of  15  minutes  to  a  maximum  of  60  minutes.
In this mode, before the passage from the current channel to the next, the "TESt-On" string is displayed followed
by  the  minutes  of  the  general  alarm  relay  being  switched  off.
You can  terminate this  mode  before the  natural deadline by resetting  the control  unit by pressing 3  consecutive
times  and  within  5  seconds  the  RESET  button.

Mantinance Test

Summary of Contents for GS300-Mc

Page 1: ...all underground car parks The GS300 Mc control unit has three danger levels 1st LEVEL 1st Alarm This was set to 8 of L E L 120ppm 2nd LEVEL 2nd Alarm This was set at 13 of L E L 200ppm 3rd LEVEL Main Alarm This was set at 20 of L E L 300ppm For oxygen the centrol unit GS300 Mc presents three levels of danger which are 1st Pre Alarm Both in deficiency and excess of Oxygen 2nd Pre alarm Both in defi...

Page 2: ...h Battery Max 2 2 Ah Optional 12 V 10 Battery Charger max 2 2 Ah Controlled Power Demand 8 3W max 230V Power Demand 4W max 12V Relay Contact Range 10A 250VAC resistive 5A 30Vdc resistive 1st Pre Alarm Set to 8 of L E L or 120ppm CO 2nd Pre Alarm Set to 13 of L E L or 200ppm CO Final Alarm Set to 20 of L E L or 300ppm CO Monitored Gas Indication Through backlit color display Number of Conventional ...

Page 3: ...one 2 Oxygen In 4 20 mA 5 Yes Yes SGF106 SemiCondut IP64 Zone 2 FREON 0 300 ppm 4 20 mA 5 Yes Yes SGF108 Elettrochimica IP64 Zone 2 H2S 0 300 ppm 4 20 mA 5 Yes Yes SGF110 Electrochemical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochemical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochemical IP66 Zone ...

Page 4: ...r 300ppm ref CO and the MAIN ALARM relay contact is closed The buzzer will issue a high frequency sound 10 FAULT LED This LED blinks when one of the connected probes is faulty if there is an interruption in the cable connection or if an error was made during wiring When this LED is blinking the device is no longer capable of detecting To reactivate the device the damaged probe must be repaired or ...

Page 5: ...s appliances The ventilation of the spaces and the elimination of combustion products are described in the UNI norms according to ART 3 LAW 1083 71 and relevant legal provisions Description of Display The BX444Mc is equipped with a display backlight color to facilitate the recognition of the state of the probe monitored The data exchange for each probe connected happens every 4 seconds 00LEL 300pp...

Page 6: ... from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the electrical system adequatelylocated and easily accessible Electrical Connections Power supply 230 VAC PH N 4 5 6 7 8 9 10 11 12 C NC NO C NC NO C NC NO C NC NO Fault 1st threshold 2nd threshold Main alarm PLEASE NOTE All relays are free of voltage Connection...

Page 7: ... 7 8 9 10 11 12 Power supply 230 VAC C NC NO C NC NO C NC NO C NC NO Fault 1 Threshold 2 Threshold Alarm Solenoid valves Ph N PH N 4 5 6 7 8 9 10 11 12 Power supply 230 VAC C NC NO C NC NO C NC NO C NC NO Fault 1 Threshold 2 Threshold Alarm Solenoid valve Connection examples Power supply 230 12V Diode 1N 5406 3 2 1 Probe 1 3 2 1 Probe 2 3 2 1 Probe 3 Solenoid valve GAS and Sirens 12 VDC 1 2 3 4 5 ...

Page 8: ...ay and is maintained for 15 seconds On the next pass the LED probe will be maintained again and the alarm will be issued In case of fault The LED of the relevant probe starts blinking and remains lit The display will show the FAU Fault fixed indication and the buzzer will issue a continuous sound until 1 The repair has been carried out 2 The relevant probe has been disabled using the micro switch ...

Page 9: ...ed The relay is energized after performing the waiting phase and switches when the GS300 Mc is in main alarm In the OFF position the positive safety function is disabled The relay is energized only when the GS300 Mc enters the state of main alarm Switch 2 Functioning Mode of main alarm relay In the ON Continuous function the relay remains closed until the RESET button is pressed In the OFF Impulse...

Page 10: ...ition of the detection sensors You can connect many types of remote probes to this unit Therefore they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest p...

Page 11: ... the 240VAC mains power is correctly connected If powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the probe cables are connected as in the drawing they have not pinched the insulating sheath Check that the voltage at the terminals 3 4 is greater than 11 VDC and less than 25 VDC Check that at the terminals 3 and 5 6 7 is present a volta...

Page 12: ...LECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the recycling of electrical and electronic equipment such as for example sales points in case you buy a new and similar product local collection points waste collection center local r...

Reviews: