Important:  Assembly  /  maintenance  of  the  appliance  must  be  carried  out  by  qualified  personnel  and  in
accordance  with applicable laws and regulations.
The  manufacturer  assumes  no  responsibility  for  the  use  of  products  that  have  to  comply  with  particular
environmental and / or installation standards.

Important note
Before connecting the equipment, it is recommended that you read the instruction manual carefully and keep
it for future reference. It is also recommended to perform the electrical connections correctly as per enclosed
drawings, observing  the instructions  and  the Standards.
N.B. Refer to the documentation in all cases where the symbol is on the side

Channel:  Beinat  gas  solutions

Electric connections also available on

CONFORMITY

Installation
and user guide

INSTALL  IN  SAFE
AREA,  NO 

 ATEX

EN 50194

EN 45544-1-3

EN 50270

EN 61010-1

Compliant  EN 60079-29-1

Installation  EN 60079-29-2

Reports issued by  TUV Italia

Control Unit 1 Conventional sensor  BX150

                                                                    Rev. 4

Through the connection of 1 remote sensor, the BX150 control unit has been designed and built according to European
regulations to flexibly detect the presence of

 

toxic and/or explosive gas.

A microprocessor is used to create a complete surveillance and control system with maximum flexibility.
Thanks to this and its other features, the BX150 is suitable for civil and industrial applications.

The BX150 control unit has two danger levels:
1

st

 LEVEL, 1

st

 Pre-Alarm. This is set at 13 % of L.E.L. for all probes.

2

nd

 LEVEL, Main Alarm. This is set at 20% of L.E.L.

Other technical features make this control unit extremely versatile and reliable; for example, by using a series of micro-
switches it is possible to:
Enable or disable the probe when not installed or when it’s faulty;
Select the type of gas to be detected (toxic or explosive);
Choose the relay functioning mode (pulsed or continuous);
Choose the main alarm relay shut-down time.

A TEST button checks the efficiency of both the unit and the connected probe to ensure total control of the BX150.
Thanks to the Omega-type format both small and large systems can be built by using the modularity of the DIN rail
in the previously set electrical panels.
In addition to the alarm signal light, it is fitted with an internal buzzer.

Summary of Contents for BX150

Page 1: ...he BX150 control unit has been designed and built according to European regulations to flexibly detect the presence of toxic and or explosive gas A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features the BX150 is suitable for civil and industrial applications The BX150 control unit has two danger levels 1st LEVE...

Page 2: ...mage the appliance Avoid abrupt temperature fluctuations Sudden temperature variations can cause condensation and the control unit could work poorly Cleaning Never clean the device with chemical products If necessary wash with a moist cloth Technical Specifications Precautions 90 mm 102 mm 112 mm 10 mm 43 65 mm 90 30 mm Cuttingpanel size Mains Power 230VAC 50 60Hz 10 Secondary Power Through Batter...

Page 3: ...eon 0 300 ppm 4 20 mA 5 Yes Yes SGF108 Electrochimical IP64 Zone 2 H2S 0 300 ppm 4 20 mA 5 Yes Yes SGF110 Electrochimical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochimical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochimical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SG800duct Catalytic IP66 Zone 2...

Page 4: ...C GAS selection LED This LED lights up when the internal micro switch is switched to CO 7 EXPLOSIVE GAS selection LED This LED lights up when the internal micro switch is switched to GAS 8 FAULT LED This LED will light up when the connected probe is faulty if there is an interruption in the cable connection or if an error was made during wiring 9 OVER LOAD LED probe overload If this LED turns on i...

Page 5: ...r performing the step of waiting and switches when the BX150 is main alarm In the OFF position the positive safety function is disabled The relay is energized only when the BX150 goes into the mainl alarm Switch 2 Working mode of the main alarm relay In the ON continuous position the relay remains closed until the N button is pressed In the OFF impulse position the relay remains closed for 20 seco...

Page 6: ...Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that signal cables should be separated from power cables An automatic cut off switch appropriately identified as device sectioning of the detector should be incorporated in the electrical system adequately located and easily acce...

Page 7: ...hold Alarm Solenoid valves Ph N 230 VAC NC NA Solenoid valve GAS and Sirens 12 VDC Powersupply 230 12V Diode 1N 5406 12 V 5 4 3 2 1 R1 3 2 1 Probe 1 If a 12Vdc solenoid valve which does not work well is connected to the BX150 Direct connection of 12VDC solenoid valves or sirens to the BX150 is not permitted An external power unit must always be used The BX150 M gives a max current of 50mA Control ...

Page 8: ...ld Alarm Solenoid valves Powersupply 230 12V Ph N 230 VAC 230 VAC Diode 1N 5406 12 V 5 4 3 2 1 R1 3 2 1 Probe 1 Electrical Connections If a 12Vdc solenoid valve which does not work well is connected to the BX150 Direct connection of 12VDC solenoid valves or sirens to the BX150 is not permitted An external power unit must always be used The BX150 M gives a max current of 50mA ...

Page 9: ...You can connect many types of remote probes to this unit Therefore they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest point of the floor in order to d...

Page 10: ...ins power is correctly connected If powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the connecting cables from the BX150 to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short ci...

Page 11: ...Page 11 NOTES ...

Page 12: ...ning shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the app...

Reviews: