Additional Installation Tips

6.3 To Achieve Better EMC Protection

Use shielded cables for RS232 communication.

Use twisted pair and shielded cabling for RS422 and RS485.

Use the cabling intended for the bus type; Ethernet, Profibus, CC-Link,
CAN, Device Net etc.

Install and connect according to applicable specifications for the relevant bus
standard.

Use shielded cabling for Ethernet, preferably with foil and a braided shield.

D-sub covers should be shielded, and the shield should be connected to the
cover 360° where the cable enters.

Connect the shield at both ends.

Shielded cable

Not same potential

Ground plane 1

Ground plane 2

Ground plate

Ground plate in another building

0.1 

μ

F/250 V

With longer distances, there is a risk that the ground potential may be different.
In that case, the shield should only be connected at one end. A good alternative
is to connect the other end of the shield to the ground via a 0.1 μF/250 V plastic
capacitor. Both ends are then connected to the ground in terms of HF, but only
connected to the ground at one end in terms of LF, thus avoiding the 50/60 Hz
grounding loops.

Metal cabinet

Metal cabinet

Terminal or connector

Terminal or connector

EMC cable gland

Plastic cable gland

Shielded cable

Short distance

Cable clamp
in steel

Shielded cable

1. Use an EMC cable gland or regular plastic cable gland, remove the outer jacket

and connect the shield to the installation plate with a 360° metal cable clamp.

2. Place the 24 V DC and communications cabling in one cable trunk/cable duct

and 230/380 V AC in another. If the cables need to be crossed, cross them at
90° only. Avoid combining the cabling for stronger 24 V DC outputs with
the communication cabling.

Ferrite cores that are snapped onto the shielded cabling may remove minor
disturbances. Large ferrite pieces that are snapped onto unshielded cabling and
where the wires go 2-4 times around the cores are approximately 5-25 times more
efficient.

Beijer Electronics, MAEN165

23

Summary of Contents for T15BR

Page 1: ...T15BR Installation Manual English MAEN165 2014 04 ...

Page 2: ... group companies assumes no responsibility for any errors that may appear in this document Read the entire installation manual prior to installing and using this equipment Only qualified personnel may install operateor repair this equipment Beijer Electronics AB including all its group companies are not responsible for modified altered or renovated equipment Becausethe equipment has a wide rangeof a...

Page 3: ...erals 11 3 TechnicalData 12 4 ChemicalResistance 14 4 1 MetalCasing 14 4 2 Touch Screen and Overlay 15 4 2 1 Autoflex EB 15 4 2 2 Touch Screen Surface 16 4 2 3 Touchscreen Protective Film 16 4 3 Terminalto PanelGasket 17 5 Operator Panel Drawings 18 5 1 Connectors 18 5 2 Communication Ports 18 5 3 T15BR Outline 19 6 Additional Installation Tips 20 6 1 Grounding the Operator Panel 20 6 2 Ethernet Co...

Page 4: ... powerful irritant Incase of skincontact wash immediately with plenty ofwater In case of eye contact holdthe eye open flush with plenty of water and get medical attention The figures in this manualserves an illustrative purpose Because of the many variables associated with any particular installation the supplier cannot assume responsibility for actual use based onthe figures The supplierneither guar...

Page 5: ...w the table with cable and torque specificationsbelow Terminal Block Connector Wire Size TQ Lb In Phoenix Contact Part No 1757022 14 20 AWG 2 08 0 52 mm2 5 7 Warning Do not open when an explosive atmosphere is present N OUVREZ PAS SI UNE ATMOSPHÈREEXPLOSIVE EST PRÉSENTE Warning Explosion hazard Do notdisconnect while circuit is live unless the area is known to be non hazardous RISQUE D EXPLOSION NE...

Page 6: ...accompanyinginstallation instructions Onlyqualified personnel may install the operatorpanel Separate the high voltage signal and supply cables Make sure that the voltage and polarity of the powersource iscorrectbefore connectingthe operatorpanel to the power outlet Peripheral equipment must be appropriate forthe application and location 1 5 During Use Keep the operatorpanel clean Emergency stopand ...

Page 7: ...ronment lithiumbattery electrolytic capacitorand display 1 8 Appearance of Air in Touch Screen The layerstructure of the touch screen contains airandinrare casesappearance of bubbles can arise This is purelycosmetic and does not affect anyfunctionality of the operatorpanel The appearance can occurundercertain environmental conditions such as temperature humidity and atmospheric pressure Beijer Ele...

Page 8: ...ace Requirements Maximum installation plate thickness 8 mm Space requirements in millimeterswhen installingthe operatorpanel 100 100 100 50 50 410 286 Note The dimensions on the drawing are not proportional Beijer Electronics MAEN165 8 ...

Page 9: ...drawingis available for download from the Beijer Electronics web site Formore information see sections Operator Panel Drawings and Technical Data 3 Secure the operator panel in position by screwingthe slotted thumb screw clockwise allowing the built in bracket to flipout and tighten againstthe cabinet Tighten the screws 12 to 0 7 Nm 0 2 Nm 4 Formost applications the provided Thumb Screw Installatio...

Page 10: ...from signal and supply cables Shielded communication cables are recommended 24V DC RS232 RS422 RS485 24V DC A D Controller Power B Ethernet C Use 14 20 AWG 2 08 0 52 mm2 wire forthe powerconnections Connect cable A Connect cable B usingan M5 steel screw with zinc plating and a groundingconductor as short as possible that issizedcorrectly accordingtolocal electrical codes Connect cable C Connect ca...

Page 11: ...achthem tostrain reliefplate with cable ties provided 2 2 3 Other Connections and Peripherals Cables peripheral equipment and accessories must be suitable forthe application and itsenvironment Forfurtherdetailsor recommendations please refertothe supplier Beijer Electronics MAEN165 11 ...

Page 12: ...9 pin D sub contact with RS232 RTS CTS chassis mounted female with standard locking screws 4 40 UNC Communication module CAN Ethernet 1 x 10 100 1000 Base T shielded RJ45 1 10 100 Base T shielded RJ45 USB 3 USB Host 2 0 maxoutputcurrent 500 mA Processor Intel Atom External storage media 1 SD card optional Flash memory application memory 4 GB iX version 16 GB PPC version Memory RAM 1 GB iX version ...

Page 13: ...esistance for more information 2 Standby mode The backlight is turned off there are no cabled interfaces and the CPU is below 5 Optional CAN module is present 3 Typical mode The backlight is fully powered there are no cabled interfaces and an application is running Optional CAN module is present 4 Estimated Maximum mode Allinterfaces are cabled all USB ports are plugged with mass storage devices t...

Page 14: ... chemicals at room temperature Butanol Nitric acid 3 Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Na hypochlorite 10 Sodium hypochlorite Turpentine Note If exposure to any of the above chemicals is demanded itis recommended to first test the chemical in a hidden spot of the metal casing The powder paint shows little or no resistance to the followingchemicals at room temp...

Page 15: ...P 60 95 1 Bleach 1 Hydrochloric acid 36 Sulfuric acid 10 Castor oil Linseed oil Tomato ketchup Caustic soda 40 1 Methanol Trichloroaceticacid 50 Cutting oil Nitric acid 10 White Spirit Cyclohexanol Paraffin oil Windex 1 Diacetone alcohol Persilpowder in solution 1 Wisk Diesel Petroleum spirit 1 1 Extremely faint glossing of the texture was noted Autoflex EBwithstands DIN 42 115 Part2 exposure ofup ...

Page 16: ...play protectionfilm thatcan be ordered from BeijerElectronics Outdoor Use In common with all polyesterbased films AutoflexEB is not suitable foruse in conditions oflong term exposure todirect sunlight Note The layer structure of the touch screen contains airand in rare cases appearance of bubbles can arise This is purely cosmetic and does not affect any functionality of the panel The appearance can o...

Page 17: ...e to the following chemicalsat room temperature Acetic acid conc Na hypochlorite 10 Ammonia 30 Nitric acid 10 Butanol Phosphoric acid 10 Ethyl acetate Phosphoric acid 20 Hydrochloric acid 37 cold Note If exposure to any of the above chemicals is demanded itis recommended to first test the chemical in a hidden spot of the gasket The flame retardant silicone rubbershowslittle orno resistance tothe fo...

Page 18: ... USB 2 USB Host 2 0 max output current 500 mA 5 Headphone Headphone Connector 6 LAN B 1 x 10 100 1000 Base T shielded RJ45 7 COM 2 RS422 RS485 Communication Port 5 2 Communication Ports Serial port 9 pin female Pin COM1 COM2 1 RS422 Tx RS485 Tx Rx 2 RS232 RxD 3 RS232 TxD 4 RS422 Rx 5 GND GND 6 RS422 Tx RS485 Tx Rx 7 RS232 RTS RS422 RTS 8 RS232 CTS RS422 RTS 9 RS422 Rx Beijer Electronics MAEN165 18...

Page 19: ... 5 3 T15BR Outline 286 410 7 max 8mm 76 9 9 392 9 268 9 B C E D A E A Connectors B SD memory card slot C USB host D Expansionport E Optional CAN module not shown CAN depth doesnotexceed heatsink Beijer Electronics MAEN165 19 ...

Page 20: ...ccordingto localelectrical codes between the operatorpanel s quick connect plinth and the panel s chassis see 2 in drawing above 2 Connect awire orgroundingbraidthat is sized correctly accordingto local electrical codes between the operator panel s chassis and the closest grounding point on the door see 3 indrawingabove 3 Connect astrongbut shortgroundingbraid betweenthe doorand the device cabinet...

Page 21: ...5 RJ45 RJ45 RJ45 Industrial Ethernet Operator panel Operator panel Operator panel Operator panel Shielded Short and unshielded 0 1 μF 250 V 1 1 3 3 8 8 2 2 In some industrialunits forEthernet the RJ45 contact s shield is connected to the chassisviaa capacitor see 1 in drawingabove The operatorpanel sEthernet shield isdirectlyconnected to the chassis see 2 in drawingabove 1 Checkwhetherthe other Et...

Page 22: ... istobreak the shield see 3 in drawing above A more elegant methodistoexpand the shielded Ethernet cablingwith a piece of unshielded Ethernetcable see 4 in drawingabove The shield canbe grounded via anexternal 0 1 μF 250 Vplastic capacitor see 5 in drawingabove Thiswillconnect the HF transientstoground Beijer Electronics MAEN165 22 ...

Page 23: ... shield to the ground via a 0 1 μF 250 V plastic capacitor Both ends are then connected tothe ground in terms ofHF but only connected to the ground at one end in terms ofLF thus avoidingthe 50 60 Hz groundingloops Metal cabinet Metal cabinet Terminal or connector Terminal or connector EMC cable gland Plastic cable gland Shielded cable Short distance Cable clamp in steel Shielded cable 1 Use an EMC...

Page 24: ... to heat The lifespan of an electrolytic capacitoris cut in halfwith an 8 10 C increase in temperature A 15 20 C temperature increase resultsin a quarter of the lifespanetc Rittal has a goodprogram for estimatingthe anticipated average temperature in the cabinet as wellas a large program for controllingthe temperature in the device cabinet An enamel coated steel cabinethas aradiant heatvalue of 5 ...

Page 25: ...LVaccording to EN 60950 protection against electric shock andUL 950 Example Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V AC relay contacts in a smaller controller Check that the clearances and creepage distances between 24 V DC and 230 V AC fulfill EN 60950 or UL 950 If not input a separate 24 V unit into the operator panel If th...

Page 26: ...nal Many peripherals includingUSBdevices will bond the terminal s signal ground 0 V to the protective earth ground Bonding signal ground and protective earth ground mayincrease electricalemissions and introduce communicationerrors Operator panel Modular controller Printer PC Different ground potential Internal 0 V GND connection PC galvanic isolation RS232 RS422 485 USB USB device Power CPU COM CO...

Page 27: ... the ground potential the shield should be connected tothe ground via 0 1 μF 250 V plastic capacitorto preventground current in the braided shield A numberof manufacturers recommendthat the shield be grounded ateach node Various manufacturers have different systems forbustermination Depending onthe recipients design the bus wires may be onthe same levelor require pull up orpull downtoensure that n...

Page 28: ...Head office Beijer Electronics AB Box 426 201 24 Malmö Sweden www beijerelectronics com 46 40 358600 ...

Reviews: