D and E States 

 

Description 

Causes 

Solution 

Priority 

Off 

Off 

Display fail or module 

off 

Disconnected module. 

No Power supply. 

Hardware failure  

Check if the module is 

completely connected to 

the backplane rack and 

if the backplane rack is 
supplied by an external 

power supply. 

On 

Off 

Normal use 

9 (Lower) 

Blinking 1x 

Off 

Active Diagnostic 

There is at least one 

active diagnostic related 

to the module NX5000 

Check what the active 

diagnostic is. More 

information can be 

found at Maintenance 

section of this 

document 

Blinking 2x 

Off 

CPU in STOP mode 

CPU in STOP mode 

Check if CPU is in RUN 

mode. More information 

can be found on CPU’s 

documentation 

Blinking 3x 

Off 

Reserved 

 

Blinking 4x 

Off 

Non fatal fault  

Failure in some 

hardware or software 

component, which does 

not have impact on the 

basic functionality of the 

product  

Check the module 

diagnostic information. 
If it is a hardware fault, 

provide the replacement 

of this part. If it is a 

software fault, please 
contact the Technical 

Support  

Off 

Blinking 1x 

Parameter error 

Check if the module 

parameters are correct 

Off 

Blinking 2x 

Loss of master 

Loss of communication 

between module and 

CPU 

Check if the module is 

completely connected to 

the backplane rack. 

Check if CPU is in RUN 

mode. 

Off 

Blinking 3x 

Reserved 

Off 

Blinking 4x 

Fatal hardware error 

Hardware error 

Contact Altus’ support 

team in case of fatal 

hardware error. 

1 (Higher) 

 

Note: 

Fatal hardware fault:

 Please contact 

Altus’ support team in case of fatal hardware fault. 

0, 1 and Numeral Characters 

The segments 0 and 1 should be normally off. These two segments will start to blink when the module is on the Diagnostic 
Mode (Electronic Tag on Display and One Touch Diag). 

RJ45 Connector LEDs 

Both LEDs placed in the RJ45 connector; identified by NET 1, help the user in the installed physical network problem detection, 
indicating the network LINK speed and the existence of interface communication traffic. The LEDs description is presented in 
the table below. 

 

Yellow 

Green 

Description 

Off 

Off  

Network LINK absent. 

On 

Off  

10Mbits/s network LINK. 

On 

On 

100Mbits/s network LINK. 

Blinking 

– 

Occurrence of Ethernet network transmission or reception, for or to this IP address. It 
blinks when 

there’s module demand, not on every transmission or reception, i.e. blinking 

frequency doesn’t correspond to data transmission or reception frequency. 

 

Summary of Contents for NX5000

Page 1: ...m with uses of network redundancy Its main features are Simultaneous support to MODBUS TCP and MODBUS RTU over TCP Simultaneous operation as MODBUS master client and server slave Redundant architectur...

Page 2: ...Nexto Series brings to PLCs is the Electronic Tag on Display This new functionality brings the process of checking the tag names of any I O pin or module used in the system directly to the CPU s graph...

Page 3: ...ge relative humidity 5 to 96 non condensing Conformal coating Yes Standards IEC 61131 2 CE 2011 65 EU RoHS 2014 35 EU LVD and 2014 30 EU EMC UL Listed UL61010 1 file E473496 DNV GL Type Approval DNVGL...

Page 4: ...ype packets in broadcast informing its IP and MAC address for all devices interconnected to the network These packets are sent during the download of a new application by the MasterTool IEC XE softwar...

Page 5: ...Ethernet Module NX5000 Nexto Series Doc Code CE114903 Revision D Altus S A 5 Physical Dimensions Dimensions in mm...

Page 6: ...Revision D Altus S A 6 Installation The following figure shows the electrical installation on the rack backplane rack All information about electrical installation mechanical assembly and module inser...

Page 7: ...all modules connections be checked and that all dust or any kind of dirt at the module s enclosure be removed at least every 6 months NX5000 offers five important features to assist the user during m...

Page 8: ...ck if the module parameters are correct 4 Off Blinking 2x Loss of master Loss of communication between module and CPU Check if the module is completely connected to the backplane rack Check if CPU is...

Page 9: ...bActiveDiagnostics TRUE Module has active diagnostics FALSE Module doesn t have active diagnostic 1 MODULE W FATAL ERROR tGeneral bFatalError TRUE Fatal error FALSE No fatal error 2 CONFIG MISMATCH tG...

Page 10: ...RD wRXErrors Receiving errors QW n 100 WORD wRXDropErrors Receiving drop errors QW n 102 WORD wRXFrameErrors Receiving frame errors Manuals For correct application MODBUS configuration and utilization...

Reviews: