106. Battery Information
Important Safety Precautions

The installer must take these precautions:

1) Wear protective clothing, eye-wear, rubber gloves and boots. Batteries contain corrosive acids or caustic alkalis and toxic 
materials and can rupture or leak if mistreated. Remove rings and metal wristwatches or other metal objects and jewelry. 
Don’t carry metal objects in pockets where the objects can fall onto the batteries or into the 

Vesta-M

 micro inverter system.

2) Tools must have insulated handles so that they will not short battery terminals. Do not allow a tool to short a battery 
terminal to another battery terminal or to the cabinet at any time. Do not lay tools or metal parts on top of the batteries, and 
do not lay any objects where they could fall onto the batteries or into the cabinet.

3) Install the batteries as described in this manual. When connecting cables, never allow a cable to short across a battery’s 
terminals or to the cabinet.

4) Keep the cable away from any sharp metal edges.

5) Install the battery leads so they cannot be pinched by the 

Vesta-M

 micro inverter system cover/door.

6) Where conductors may be exposed to physical damage, protect conductors in accordance with 

NEC

 requirements.

7) Full voltage and current are always present at the battery terminals. The batteries used in this system can produce 
dangerous voltages, extremely high currents, and possible risk of electric shock. Batteries may cause severe injury if the 
terminals are shorted together or to ground (earth). Be extremely careful to avoid electric shock and burns caused by 
contacting battery terminals or shorting terminals during battery installation. 
Do not touch uninsulated battery terminals.

8) A qualified electrician who is familiar with battery systems and required precautions must install and service the batteries. 
Any battery used with this unit shall comply with the applicable requirements for batteries in the standard for emergency 
lighting and power equipment, UL 924. Cabinets are designed to be used with, and batteries must be replaced by identical 
cells or a Manufacturer approved equivalent. If using substitute batteries not supplied by the Manufacturer, the unit’s UL 
listing will be void, and the equipment may fail to perform properly. 

The installation must conform to national and local codes as well. Keep unauthorized personnel away from batteries.

106.1 Tools

The following tools are required to install the system batteries:
Long Nose Pliers, Digital Volt-Ohm Meter, Safety Glasses

CAUTION: Always use insulated tools for battery installation. 

106.2 Battery Installation and Connection

1) 

Lead-Calcium Battery Models: VST-M-32

 and 

VST-M-55

 are supplied with a single 12Vdc Lead Calcium battery.  To 

install the unit battery, place the battery within the system housing and connect the black battery negative fly lead to the 
battery’s black  (B-) terminal. Connect the red battery positive fly lead to the battery’s red (B+) terminal.

2) 

Nickel Cadmium Battery Models: VST-M-20

 and 

VST-M-35

 

are supplied with a single 12Vdc

 Nickel Cadmium battery.  

To install the unit battery, place the battery within the system housing and connect the black battery negative fly lead to the 
battery’s black (B-) lead wire. Connect the red battery positive fly lead to the battery’s red (B+) lead wire.

Summary of Contents for Vesta-M Micro

Page 1: ...verter Power Systems Lead Calcium Battery Models VST M 32 and VST M 55 Nickel Cadmium Battery Models VST M 20 and VST M 35 Surface S Recessed R and Ceiling T Grid T Mounted versions Beghelli USA 3250 Corporate Way Miramar FL 33025 TEL 954 442 6600 FAX 954 442 6677 ...

Page 2: ...ounted securely in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the MANUFACTURER may cause an unsafe condition The AC voltage rating of this equipment is specified on the product label Do not connect equipment to any other voltage Do not use this equipment for other than its intended purpose...

Page 3: ... R Models Cabinet Mounting Ceiling T Grid T Models AC Connections AC Wiring Preparations AC Input Voltage Selector Plug Installation AC Input output Wiring Connections to Terminal Block Battery Information Tools Battery installation and Connection Battery Voltage Check Final Installation Checklist System Start Up Procedure System Test 4 5 5 5 5 5 5 6 6 6 6 6 7 7 8 8 9 9 10 10 10 11 11 11 11 Safe S...

Page 4: ...ickel Cadmium Battery charger Fully automatic dual mode with temperature compensation Recharge time Meets UL requirements 96 Hours Battery protection Automatic low battery voltage disconnect and reverse polarity protection Standard batteries Sealed Lead Calcium 7 year life Sealed Nickel Cadmium 15 year life Battery voltage 12Vdc all models Runtimes 90 minutes standard Operating temperature Lead Ca...

Page 5: ... 5 cm 4 3 8 11 1 cm 13 5 9 VST M 32 S Ceiling Recessed 1 23 7 8 60 6 cm 6 1 4 15 8 cm 8 0 20 4 cm 15 6 8 VST M 55 S Ceiling Recessed 1 23 7 8 60 6 cm 6 1 4 15 8 cm 8 0 20 4 cm 19 8 6 VST M 20 S Ceiling Recessed 1 23 7 8 60 6 cm 6 1 4 15 8 cm 8 0 20 4 cm 12 5 4 VST M 35 S Ceiling Recessed 1 23 7 8 60 6 cm 6 1 4 15 8 cm 8 0 20 4 cm 13 5 9 HOUSING DIMENSIONS SYSTEM WEGHT System weight shown include i...

Page 6: ...ee batteries The gas is vented through the vent caps and into the air Do not allow amosking sparks or flames in battery storage location because hydrogen is concentrated under the vent cap of each cell of the battery Hydrogen is highly explosive and is hard to detect because it is colorless odorless and lighter than air 103 Installation Requirements 103 1 Operating Environment Install the Vesta M ...

Page 7: ...ltitude Operation The maximum operating temperature drops 1 Celsius per 300 meters 2 F per 1000 feet above sea level Maximum elevation is 3000 meters 10 000 feet 104 Cabinet Mounting 104 1 Tools Required The following tools are required to install the system Socket Set Phillips Screwdriver Diagonal Wire Cutters Long Nose Pliers Electrical Tape Digital Volt Ohm Meter Safety Glasses with Side Shield...

Page 8: ...ls provide knockouts on the top and right hand side of the unit Additional entry points if required can be added using a metal punch Do not drill into the cabinet as metal filings can cause short circuits and damage the equipment Note Consider unit knockout locations prior to mounting unit Allow room for easy routing of conduit to entry point 104 4 Surface Mount S Models 1 Remove cover and any pac...

Page 9: ...sed and left open will void the plenum rating of the unit 3 Mount the unit securely in place between T Grid members NOTICE Safety chain or cable rated 50 pound minimum working load 250 pound minimum breaking strength is required to hang the unit in a T Grid system Failure to correctly install unit will cause an unsafe condition 1 Remove cover and any packing material inside unit housing that may h...

Page 10: ...C Wiring Preparations 1 Remove the system s front cover 2 Make sure the Vesta M micro inverter system input and output voltages are correct for the particular application Remember that the Vesta M micro inverter system provides single phase power only 3 The input circuit breaker in the input service panel provides the means for disconnecting AC to the Vesta M micro inverter system Only authorized ...

Page 11: ...it void the warranty and may cause a dangerous or unsafe condition 105 3 AC Input Output Wiring Connections to Terminal Block Depending on how the fixture load is to be operated wire the systems as described below Normally On Operation connected fixture s remain illuminated in AC and emergency modes See Wiring Diagram 1 Normally Off Operation connected fixture s illuminate only upon loss of utilit...

Page 12: ...ic shock and burns caused by contacting battery terminals or shorting terminals during battery installation Do not touch uninsulated battery terminals 8 A qualified electrician who is familiar with battery systems and required precautions must install and service the batteries Any battery used with this unit shall comply with the applicable requirements for batteries in the standard for emergency ...

Page 13: ... Voltage Selector Plug in the position that does not match the AC input line voltage will damage the unit void the warranty and may cause an dangerous or unsafe condition 108 System Start Up Procedure IMPORTANT The Vesta M Micro inverter system is a sophisticated electronic backup power supply Care must be taken to follow the steps below in their exact sequence Failure to do so may result in possi...

Page 14: ...on follow the System Start up Procedure outlined in Section 108 Be sure to complete all of the steps to assure the unit will operate properly 200 2 Routine System Maintenance The Vesta M micro inverter system unit is designed to provide years of trouble free operation The unit does require some routine attention to assure peak performance The Manufacturer recommends a Preventative Maintenance chec...

Page 15: ...tity and type of battery as replacements Substituting batteries not supplied by the Manufacturer will void the UL listing of the system and may cause equipment failure To ensure the superior performance of your Vesta M micro inverter system and to maintain proper charger operation replace spent batteries only with those having the same part number voltage and ampere hour rating as the original bat...

Reviews: