IMPORTANT: Indicator (LED light) illuminated indicates battery in charge mode when AC power is applied.

 It is recommended and 

required by applicable code to test emergency function to ensure proper operation of the system; push the test switch for 

thirty (30) seconds every 30 days to ensure the emergency driver is functioning as LED light source illuminated. Conduct a 

ninety minute (90)discharge test one time (1) per year; LED light source should be illuminated for a minimum of ninety minutes (90).

1. EM Test: 

Press and hold test button to enter EM mode for testing, in all normal AC powered situations including 

low power standby modes. 

2. Manual Self-Diagnostic: 

quick press the test button three times within three seconds to force the controller to 

enter a Self-Diagnostic cycle. To quit the self-diagnostic cycle after engaged press and hold the test button for 

five seconds. 

3. Enable/Disable Auto Self-Diagnostic: 

Press and hold the test button for two seconds, then release and quickly 

press the test button two times, then release and press and hold the test button for two more seconds. When 

properly executed the indicator on the test button will display the appropriate Enable/Disable status. A flashing 

of 2.5s ON/0.5s OFF mean "Enabled", while a flashing of 0.5s ON/2.5s OFF means "Disabled". Once Enable/Disable 

is set the status color on the test button will remain the same throughout normal operation (refer to LED INDICATOR 

LEGENDS). 

LED INDICATOR / TEST SWITCH

LED INDICATOR LEGENDS

TEST SWITCH OPERATIONS