Beghelli NVG Instruction Manual Download Page 3

NVGEW V90800L / V90801L / V90802L / V90803L / V90805L 

INSTRUCTION MANUAL 

E09060060 / 1494.0409E / V. 1.8

 

Beghelli PRÄZISA GmbH 

Page 3 of 5 

E-mail: 

[email protected]

 Internet: 

www.beghelli.de

 

 

* REMARKS: 

 

ATTENTION ! 

 

>

 

CONNECT

 

LOAD

 

AT

 

FIRST

 

BEFORE

 

SWITCHING

 

ON

 

NET

 

AND

 

BATTERY

 

VOLTAGE 

 

>

 

TOTAL

 

OUTPUT

 

POWER

 

(OUT1 + OUT2): 

 

Incandescent lamps:

 

max. 120 W 
 

Fluorescent lamps with inductive control gear:

 

max. 120 W, 
the DIP switch SW1 must be set at „AC/DC OUT“ in the position 

OFF

possibly present compensation capacitors must be removed from J32 and J33, 
compensation capacitors can be connected to J34 or J35 if required 
 

Fluorescent lamps with electronic control gear: 

max. 120 W, 
the DIP switch SW1 must be set at „AC/DC OUT“ in the position 

ON

 

 

>

 

USE

 

WITHOUT

 

CENTRAL

 

(LOGICA

 

S

 

OR

 

LOGICA

 

FM): 

The DIP switch SW1 must be set at „BS/DS“ in the position 

OFF

 for the use of light switches on J25 / J26 or to implement the operating mode non-

maintained operation. The DIP switch SW1 must be set at „BS/DS“ in the position 

ON

 to implement the operating mode maintained operation. 

 

>

 

USE

 

WITH

 

CENTRAL

 

(LOGICA

 

S

 

OR

 

LOGICA

 

FM): 

The function AUTODIMMER must be assigned over the central (Logica S or Logica FM) to the NVG for the use of light switches on J25 / J26. The position 
of the DIP switch 1 on SW1 is not relevant. 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

CAPACITORS 

MAGNETIC CONTROL GEAR 

NVG 

STARTER 

STARTER 

ILLUMINANT 

230 V AC IN 

OUT2

OUT1

ILLUMINANT 

MAGNETIC CONTROL GEAR 

Summary of Contents for NVG

Page 1: ...V AC 50 Hz sinus voltage Output voltage emergency operation 230 V AC 50 Hz square voltage or 230 V DC 0 Hz TOTAL OUTPUT POWER OUT1 OUT2 Incandescent lamp max 120 W Fluorescent lamp max 120 W inductive control gear adjust AC OUT see page 3 electronic control gear adjust DC OUT see page 3 Output circuit fuses 250 V 1 A time lag 5x20 mm Battery type lead acid battery Battery block voltage 12 V Batter...

Page 2: ...7 DALI CTRL not used not used 8 AUX normal operation not allowed SW1 SW2 DIP Name OFF ON 1 BATT_0 battery capacity 13 Ah battery capacity 13 Ah 2 BATT_1 not used not used 3 LOAD_0 OUT1 power 10 W OUT1 power 10 W 4 LOAD_1 OUT2 power 10 W OUT2 power 10 W ROTARY SWITCH SW3 set always in position 0 FUSES 250 V 1 A time lag 5x20 mm 230V AC OUT max 300 W bridged with J34 INPUT 1 230 V AC light switch ON...

Page 3: ... Fluorescent lamps with electronic control gear max 120 W the DIP switch SW1 must be set at AC DC OUT in the position ON USE WITHOUT CENTRAL LOGICA S OR LOGICA FM The DIP switch SW1 must be set at BS DS in the position OFF for the use of light switches on J25 J26 or to implement the operating mode non maintained operation The DIP switch SW1 must be set at BS DS in the position ON to implement the ...

Page 4: ...BLINKING LED loss of the synchronicity at test procedure NVG off because of a too long mains failure To remedy this failure a test synchronisation and a reset must be done by central or autotest command GREEN GREEN GREEN 250 250 250 250 250 250 250 250 250 RED 250 250 250 RED GREEN GREEN GREEN 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 GREEN GREEN GREEN RED RED 250 250...

Page 5: ...ION MANUAL E09060060 1494 0409E V 1 8 Beghelli PRÄZISA GmbH Page 5 of 5 E mail kontakt beghelli de Internet www beghelli de AUTOTEST COMMANDS DURATION INTERVALS COMMAND test synchronism and reset immediate test duration test stop all tests will be stopped ...

Reviews: