Beghelli NVG Instruction Manual Download Page 1

NVGEW V90800L / V90801L / V90802L / V90803L / V90805L 

INSTRUCTION MANUAL 

E09060060 / 1494.0409E / V. 1.8

 

Beghelli PRÄZISA GmbH 

Page 1 of 5 

E-Mail: 

[email protected]

 Internet: 

www.beghelli.de

 

Emergency supply device NVG for the LOGICA system

 

 
 

Type: NVGEW 
Order codes: 

V90800L (6,5 Ah) 

 V90801L 

(13 

Ah) 

 

V90802L (28 Ah) 

 V90803L 

(40 

Ah) 

 V90805L 

(55 

Ah) 

 

Technical data:

 

Mounting: surface wall mounting 
 
Body: ABS, plastic 
 
Mains supply: 198 V AC to 254 V AC / 50 Hz 
 
Ambient temperature: 0 °C to 40 °C 
 
Output voltage (mains operation): 230 V AC / 50 Hz (sinus voltage) 
 
Output voltage (emergency operation): 230 V AC / 50 Hz (square voltage) 

                                                              or 

                                                              230 V DC / 0 Hz 
 

TOTAL

 

OUTPUT

 

POWER (OUT1 + OUT2): 

Incandescent lamp: 

max. 120 W

 

Fluorescent lamp: 

max. 120 W

 

- inductive control gear:

 adjust „AC OUT“ (see page 3) 

- electronic control gear:

 adjust „DC OUT“ (see page 3) 

 
Output circuit fuses: 250 V / 1 A / time-lag / 5x20 mm 
Battery type: lead acid battery 
Battery block voltage: 12 V 
Battery capacity: 6,5 Ah / 13 Ah (2x 6,5 Ah) / 28 Ah / 40 Ah / 55 Ah, 
                            depending on model 
Duration (emergency lighting) : 1 h or 3 h (adjustable) 

 

 
 
 
 
 

V90800L 
V90801L 

V90802L 

V90803L 
V90805L 

At the model V90805L the NVG body must be 
mounted in a way that the connection poles of the 
battery block are are located at the top! 

Summary of Contents for NVG

Page 1: ...V AC 50 Hz sinus voltage Output voltage emergency operation 230 V AC 50 Hz square voltage or 230 V DC 0 Hz TOTAL OUTPUT POWER OUT1 OUT2 Incandescent lamp max 120 W Fluorescent lamp max 120 W inductive control gear adjust AC OUT see page 3 electronic control gear adjust DC OUT see page 3 Output circuit fuses 250 V 1 A time lag 5x20 mm Battery type lead acid battery Battery block voltage 12 V Batter...

Page 2: ...7 DALI CTRL not used not used 8 AUX normal operation not allowed SW1 SW2 DIP Name OFF ON 1 BATT_0 battery capacity 13 Ah battery capacity 13 Ah 2 BATT_1 not used not used 3 LOAD_0 OUT1 power 10 W OUT1 power 10 W 4 LOAD_1 OUT2 power 10 W OUT2 power 10 W ROTARY SWITCH SW3 set always in position 0 FUSES 250 V 1 A time lag 5x20 mm 230V AC OUT max 300 W bridged with J34 INPUT 1 230 V AC light switch ON...

Page 3: ... Fluorescent lamps with electronic control gear max 120 W the DIP switch SW1 must be set at AC DC OUT in the position ON USE WITHOUT CENTRAL LOGICA S OR LOGICA FM The DIP switch SW1 must be set at BS DS in the position OFF for the use of light switches on J25 J26 or to implement the operating mode non maintained operation The DIP switch SW1 must be set at BS DS in the position ON to implement the ...

Page 4: ...BLINKING LED loss of the synchronicity at test procedure NVG off because of a too long mains failure To remedy this failure a test synchronisation and a reset must be done by central or autotest command GREEN GREEN GREEN 250 250 250 250 250 250 250 250 250 RED 250 250 250 RED GREEN GREEN GREEN 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 GREEN GREEN GREEN RED RED 250 250...

Page 5: ...ION MANUAL E09060060 1494 0409E V 1 8 Beghelli PRÄZISA GmbH Page 5 of 5 E mail kontakt beghelli de Internet www beghelli de AUTOTEST COMMANDS DURATION INTERVALS COMMAND test synchronism and reset immediate test duration test stop all tests will be stopped ...

Reviews: