MAINTENANCE
1. The Code requires that the equipment be tested every 30 days for 30 seconds, and that written records be maintained for all test
results and repairs. Further, the equipment is to be tested once a year for the required duration as per Code. The battery is to
be replaced or the equipment to be repaired whenever the equipment fails to operate as intended during the duration test. The
manufacturer strongly recommends compliance with all Code requirements.
2. Clean lenses on a regular basis to provide maximum light distribution in case of an emergency.
NOTE:
The servicing of any parts
should be performed by qualified service personnel only. The use of replacement parts not furnished by the manufacturer, may
cause equipment failure and will void the warranty.
TROUBLESHOOTING
EMERGENCY LAMPS DO NOT COME ON
AC On Light is out before test...
1. Check AC supply - be sure unit has 24 hour AC supply (un-switched).
2. The AC supply is OK, and the indicator light is out, replace charger board.
The Charge Light is on before test...
1. The battery could be severely discharged. Allow 24 hours for recharge and then retest.
2. If charging the battery didn’t work, the output could be shorted or overloaded, or the battery not connected.
NOTE:
This could be the result of a switched AC supply to the unit (which has been turned off at some point), a battery with a shorted
cell, an old battery or a battery which has been discharged due to a long power outage and is not yet fully recharged.
EMERGENCY LAMPS COME ON DIM WHEN TEST BUTTON IS PRESSED
The battery is discharged - permit unit to charge for 24 hours and then retest. If lamps are still dim, check the charger for proper func-
tion. If the charger functions correctly, replace the battery.
EMERGENCY LAMPS COME ON WHEN BATTERY IS FIRST CONNECTED
The battery may be connected in reverse polarity. Check connections. Connect Positive lead to Positive battery terminal and Negative
lead to Negative battery terminal. The lamps should then turn off and the charge indicator should light when the AC power is applied.
(Fig.3)
NOTHING HAPPENS WHEN THE UNIT IS ENERGIZED
Some models have a standard time delay built into the design of the charger board. Please allow 15
minutes with AC current connected. At this point the LED AC-ON and CHARGE lights should illuminate.
NOTE:
This condition may also be caused by incorrectly connecting a 120 Volt supply line to the 347-Volt transformer lead.
SAVE THESE INSTRUCTIONS
926000232
BeLuce Canada Inc., 3900 14th Avenue, Markham, ON L3R 4R3 Tel: (905) 948-9500 Fax: (905) 948-8673
07/08/2021
Figure 1.
Battery
Figure 2.
Figure 3.
Figure 5.
2 Batteries in
series
2 Batteries in
parallel
Figure 4.
Test
347V (Red) or 277V (Orange)
120V (Black)
COM (White)
GND (Green)
Charge
AC On
Fuse
Circuit board
Battery
Lamps
Wall Mount
Conduit (not supplied)
Conduit stem
mount adapter
Pendant Mount