background image

TROUBLESHOOTING 

EXIT SIGN DOES NOT COME ON AT ALL

1.   Check AC supply and all AC connections - be sure exit has 24 hour AC supply (unswitched).

2.   Check supply voltage and AC connections. The AC supply must be at least 80% of nominal (96V on a 120V line)

 

for equipment to function normally. At lower voltages the LEDs will begin to glow dimly until the source voltage

 

drops below the full “turn-on” point.

NOTE:   This condition may also be caused by incorrectly connecting a 120 Volt supply line to the

 

 

277-Volt capacitor assembly lead.

3.   AC supply is OK ; replace LED circuit board assembly

SAVE THESE INSTRUCTIONS

MAINTENANCE 

1.  

Code requires that the equipment be tested every 30 days for 30 seconds, and that written records be maintained.

 

Further, the equipment is to be tested once a year for the duration required as per Code. The equipment is to be repaired

 

whenever the equipment fails to operate as intended during the duration test. Written records of test results and any

 

repairs made must be maintained. BeLuce Canada Inc. strongly recommends compliance with all Code requirements.

2.  

Clean exit face(s) on a regular basis.

NOTE:   The servicing of any parts should be performed by qualified service personnel only. The use of replacement

 

 

parts not furnished by BeLuce Canada Inc., may cause equipment failure and will void the warranty.

926000141

Figure 1

Figure 4

Frame

Faceplate

Electrical 

Junction Box 

(supplied by 

others)

Figure 2

Pull hinged faceplate 

down and open

Figure 3

Figure 5

3/4” to 1”

Insert screwdriver 

inbetween faceplate 

and exit frame

Universal 

Spiderplate

Exit Canopy

Faceplate 

latch strike

Ensure that face-

plate latch strike 

remains at 90°

90°

Chassis GND

LED Board

AC ONLY SIGN

Chassis GND

GREEN Ground

BLACK 120VAC

RED 347VAC or ORANGE 200-277VAC

WHITE Neutral

LED Board

AC & UNIVERSAL DC SIGN

YELLOW Positive 6 to 24VDC

PURPLE Negative

Emergency Supply

FROM Battery Pack

SELF-POWERED SIGN

Chassis GND

24 hours

Unswitched Supply

GREEN Ground

BLACK 105 to 360VAC

WHITE Neutral

LED Board

DUAL UNIVERSAL AC SIGN

From Generator OR

Emergency Supply

BROWN 105 to 360VAC

BLUE Neutral

NOTE: Cap unused AC Wire!

NOTE: Cap unused AC Wire!

24 hours

Unswitched Supply

GREEN Ground

BLACK 120VAC

RED 347VAC or ORANGE 200-277VAC

WHITE Neutral

24 hours

Unswitched Supply

Chassis GND

LED Board

NOTE: Cap unused AC Wire!

GREEN Ground

BLACK 120VAC

RED 347VAC or ORANGE 200-277VAC

WHITE Neutral

24 hours

Unswitched Supply

Ni-Cd

Battery

BeLuce Canada Inc., 3900 14th Avenue, Markham, ON L3R 4R3 P: (905) 948-9500 F: (905) 948-8673