B6031I Series Deep well Pump Inverter User Manual
18
7.2.2 System Debugging Procedure
Figure7.2.2 Debugging flow diagram
7.2.3 Relevant Parameter Setting
Sheet 7.2.1 Parameter setting of the water-level of deep well auto controlling and constant pressure water supply
Function
Code
Factory
Setting
Recommend
Description
b00.02
3.0
xx.x
Set value of pump outlet pressure
b00.03
1
x
According to the connecting motor setting, the single phase
motor is set to 1, three phase motor is set to 0
b00.04
0
x
Motor rotating direction, set according to the actual motor
wiring of spot. Make sure the motor is running in forward
direction
b00.05
1
x
Restart after Power-on, Considering unattended management,
set to 1
b00.06
5
5
Choose the water-level of deep well auto controlling and
constant pressure water supply
b00.07
16.0
xx.x
Setting according to the rated measuring range of the pressure
transmitter
b00.08
10.0
x.x
High water pressure alarm value, Prevent system from damage
caused by high water pressure
b00.09
0.5
x.x
Low water pressure alarm value, prevent pump from damage
caused by an hydrous idling
b00.10
20
xxx
After running for a preset time when the water pressure is low,
the controller halts and alarms to prevent the pump from idling