Testing – 6
6–23
47 Negative Sequence Overvoltage
VOLTAGE INPUTS:
Configuration V1 (Modified)
CURRENT INPUTS:
Configuration C1
TEST SETTINGS:
Pickup
P
Volts
(5 to 180)
Time Delay
D
Cycles
(1 to 8160)
Programmed Outputs
Z
Output
( 1 to 8)
Function 59, 27, 79
Disable
■
■
■
■
■
NOTE:
Although no current input is required for the testing of the 47 function, it is suggested that Nominal
Current be applied to restrain the functions which use both voltage and current inputs for operation.
If other functions operate during these tests, they will need to also be disabled for the test and re-
enabled after the tests are complete.
1.
Disable functions as shown. Refer to Section 3.2, Configure Relay Data, for procedure.
2.
Confirm settings to be tested.
3.
The modification of V1 connection to to exchange voltage source V2 and V3 connections. The
resulting configuration will be Phase B voltage, supplied from voltage source 3, and Phase C
voltage, supplied from voltage source 2.
4.
Pickup Test
: Apply 3-phase voltage 5 volts below pickup
(P)
. Hold the
TARGET RESET
button in
and slowly increase the voltage applied until the
47 NEG SEQ OVERVOLTAGE
LED lights or the
pickup indicator operates on the computer target screen. The level should be equal to
P
volts ±0.5
volts or
&
5%. Release the
TARGET RESET
button and decrease applied voltage, and the
OUTPUT
LED will go out. Press the
TARGET RESET
button again to remove targets.
5.
Time Test:
Apply voltage 10% less than pickup (
P
) to all three phases. With output contacts
connected to a timer, apply
P
+ 10% volts and start timing. The contacts will close after
D
cycles,
within –1 to +3 cycles or
&
3%.
6.
If testing is complete, enable any functions disabled for this test. If other tests are to be completed,
check the proper functions to disable for the next test and proceed from this point.
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...