Commissioning
Infrastructure for EtherCAT/Ethernet
43
Version: 2.1
Fig. 36: Fluke DTX1800 screenshots
Note
Detection of interference
In the operating mode ‘Monitor’, the DTX1800 can detect interspersed interference on the
transmission link. To do this, the link must be taken out of operation and a test device con-
nected at both ends.
4.3.2
Use of the DTX1800/DSX5000
Note
Changing the settings
A product from a third party manufacturer is described in the following chapter. The respec-
tive operating manual is to be given priority. The data given below for the measuring device
settings were valid at the time of preparing this documentation – it is possible, however,
that the manufacturer of the measuring device may have changed the firmware/program
user interface at short notice.The notes below should be considered to be supplementary to
the manufacturer’s own operating manual.
The use of the FLUKE DTX1800 for the certification of Ethernet transmission links is described below as an
example.
Measuring
• Connect the main and remote device with the cable section
◦ channel adaptor DTX-CHA001A or
◦ patch adaptor DTX-PC5ES recommended
• switch both on; charge up beforehand if necessary or operate with the power supply units
• Selector switch to
AutoTest
• Press
Test
•
Save
after the test if necessary
Changing the settings
• Selector switch to
Setup
• Change settings, e.g. test limit, see manufacturer documentation
• Selector switch to
AutoTest