Product description
EL2912
18
Version: 1.0.0
3.5
Safe output
The safe outputs are implemented as a single channel per module. It is essential to pay attention to the
following note if two or more outputs run in a common sheathed cable.
DANGER
Clocked signals inside a sheathed cable
If clocked signals from different modules are used inside a single sheathed cable, then a module error such
as a cross-circuit or external power supply must lead to the switch-off of all of these modules. This is
achieved by setting the
Module Fault Link active
parameter for all modules involved. This parameter is set
to TRUE by default.
3.6
Fuse
Power supply of the power contacts
The safe outputs are supplied from the power contacts. The current carrying capacity of the power contacts
is limited to 10 A. The power supply of the power contacts for each potential group must be protected with a
10 A fuse.
3.7
Dimensions
Fig. 5: EL2912 - Dimensions
Width: 12 mm (side-by-side installation)
Height: 100 mm
Depth: 68 mm