Programming
TX1200
30
Version: 1.1
6.2.4
MP_DamperLinearActuator
This function block is used to control and monitor an actuator of a damper and of a globe valve.
MP_Address
is used to specify the MP-Bus device with which the function block is to communicate.
bStart
activates communication with the MP-Bus device.
bBusy
indicates that the function block is active. If
bStart
remains TRUE, the device is addressed cyclically with a period specified by the time in
TMPolling
. The time
should be set longer than 1 s.
bError
is used to indicate an error in communication with the actuator. The
type of the error can be read with
iErrorID
.
A positive edge at
bReset
clears any pending error messages from the actuator. This resets errors that
affect the output variables
bErr_MecOcld
,
bErr_ActHunt
and
bErrMecTrv
. If the error itself is still present,
the actuator will set these error bits again.
SetPoint
is used to adjust the position of the damper from 0...100 %. The current position of the actuator can
be read through
ActValue
.
If a sensor is connected to the actuator, its type is to be indicated in
iSensorTyp
. If no sensor is connected,
the value "0" should be entered, or the variable left open. A digital sensor should be parameterized with "1".
The state of the sensor can be queried through
bMP_Sensor_Digi
. Analog sensors "2...6" are output in
variable
iMP_Sensor_Analog
.
VAR_INPUT
MP_Address : USINT := 1;
bStart : BOOL;
bReset : BOOL;
iSensorTyp : INT;
SetPoint : USINT;
strDataKL6771 : DataKL6771;
TMpolling : TIME := t#10s;
MP_Address:
MP-Bus address of the slave.
bStart:
a positive edge starts the function block. If this remains continuously TRUE, the function block will be
activated cyclically with a period specified by the time in
TMPolling
.
bReset:
a positive edge resets the actuator's error messages.
iSensorTyp:
0: no sensor connected, 1: digital sensor connected, 2: analog sensor connected (0...35 V),
3...6: output of a resistance in ohms (3...5 applies to PT1000, NI1000 and NI1000LuS; 6 applies to NTC). To
convert to a temperature, use the corresponding conversion functions.
SetPoint:
0...100 % the set damper position specified for the actuator.
strDataKL6771:
the data structure with which the
function block must be linked (see
).
TMpolling:
the time for which the function block should address the actuator. Default 10 s, minimum time
1 s.