Programming
TX1200
47
Version: 1.1
6.2.14
MP_RoomSensor
This function block is used to read room sensors. For more information please visit
.
MP_Address
is used to specify the MP-Bus device with which the function block is to communicate.
bStart
activates communication with the MP-Bus device.
bBusy
indicates that the function block is active. If
bStart
remains TRUE, the device is addressed cyclically with a period specified by the time in
TMPolling
. The time
should be set longer than 1 s.
bError
is used to indicate an error in communication with the actuator. The
type of the error can be read with
iErrorId
.
VAR_INPUT
MP_Address : USINT := 1;
bStart : BOOL;
bReadDISensor : BOOL;
strDataKL6771 : DataKL6771;
TMpolling : TIME := t#10s;
MP_Address:
MP-Bus address of the slave.
bStart:
a positive edge starts the function block. If this remains continuously TRUE, the function block will be
activated cyclically with a period specified by the time in
TMPolling
.
bReadDISensor:
if TRUE, the DI sensor is read and the result is available in
bDigitalInput
.
strDataKL6771:
the data structure with which the
function block must be linked (see
).
TMpolling:
the time for which the function block should address the actuator. Default 10 s, minimum time
1 s.
VAR_OUTPUT
bBusy : BOOL;
bError : BOOL;
iErrorId : MP_Error;
rSensTemp : LREAL;
rDewPointTemp : LREAL;
rHumid : LREAL;
uiCo2 : UINT;
stUnit : STRING;
bDigitalInput : BOOL;
bSensorError : BOOL;
st_SensorType : STRING;
bBusy:
This bit is set for as long as the block is active.
bError:
The output becomes TRUE as soon as an error occurs. The error is described via the variable
iErrorId
.
iErrorId:
The output issues an error code when an error occurs (see
). Simultaneously
bError
is TRUE.
Summary of Contents for TwinCAT 2 TX1200
Page 1: ...Manual EN TX1200 TwinCAT 2 PLC Library TcMPBus 2022 06 02 Version 1 1...
Page 2: ......
Page 79: ......