Product overview
SCT7xxx
18
Version: 1.2
Split-core current transformers
Fig. 9: SCT6xxx
The separable measuring system of the SCT6xxx split-core current transformers enables flexible retrofitting
without disconnecting the primary conductor. Due to the minimal installation effort, they are suitable for use
in places that are difficult to access or where space is limited. Four sizes are available. Accuracy class 3 is
suitable for primary currents from 60 to 150 A, accuracy class 1 for 200 to 1000 A.
Split-core current transformers
SCT6101
Accuracy class 3,
primary current 0…60 A AC to 0…150 A AC,
secondary current 1 A AC,
max. diameter round conductor 18.5 mm (size 1)
SCT6311
Accuracy class 1,
primary current 0…200 A AC / 0…250 A AC,
secondary current 1 A AC,
max. diameter round conductor 18.5 mm (size 3)
SCT6321
Accuracy class 0.5,
primary current 0…200 A AC / 0…250 A AC,
secondary current 1 A AC,
max. diameter round conductor 18.5 mm (size 3)
SCT6411
Accuracy class 1,
primary current 0…300 A AC to 0…500 A AC,
secondary current 1 A AC,
max. diameter round conductor 27.9 mm (size 4)
SCT6421
Accuracy class 0.5,
primary current 0…400 A AC / 0…500 A AC,
secondary current 1 A AC,
max. diameter round conductor 27.9 mm (size 4)
SCT6615
Accuracy class 1,
primary current 0…600 A AC / 0…750 A AC,
secondary current 5 A AC,
max. diameter round conductor 42.4 mm (size 6)
SCT6625
Accuracy class 0.5,
primary current 0…600 A AC / 0…750 A AC,
secondary current 5 A AC,
max. diameter round conductor 42.4 mm (size 6)
SCT6715
Accuracy class 1,
primary current 0…800 A AC / 0…1000 A AC,
secondary current 5 A AC,
max. diameter round conductor 2 x 42.4 mm (size 7)
SCT6725
Accuracy class 0.5,
primary current 0…800 A AC / 0…1000 A AC,
secondary current 5 A AC,
max. diameter round conductor 2 x 42.4 mm (size 7)