Application example
SCT5xxx
37
Version: 1.0
system-related leakage currents are mainly capacitive. However, the RCD cannot distinguish between the
different leakage currents. Therefore, it can already trip when the sum of all system-related leakage currents
is above the tripping threshold. This is also possible during normal operation.
Fig. 25: Electrical equivalent circuit diagram of a speed-controlled motor
As shown in the figure, different frequency components can occur in the differential current from DC up to
several kHz. When analyzing the measured differential current, the system-related differential current must
always be considered as well, because this is present despite perfect insulation and cannot be technically
separated. Also, due to inductances (e.g. motor), high current peaks can be generated during the switch-on
processes, which can lead to relay tripping at the RCDs and RCMs.
In general, the different frequency components can be interpreted as follows:
Frequency
Typical causes
50 Hz
Power supply, mains filter (low-pass), interference suppression capacitors
50 Hz + 150 Hz
Single-phase frequency converter with internal EMC filter
150 - 1050 Hz
Three-phase frequency converter with internal EMC filter
2k - 50k Hz
Long shielded motor cable
50k - 150k Hz
Insufficient EMC filter
2k - 150k Hz
Long shielded motor cable + insufficient EMC filter
When commissioning a differential current monitor, it is important to know the actual system-related leakage
current. Only in this way can appropriate warning thresholds and relay tripping thresholds be sensibly set.
Summary of Contents for SCT Series
Page 2: ......
Page 4: ...Table of contents SCT5xxx 4 Version 1 0...
Page 25: ...Technical data SCT5xxx 25 Version 1 0 Fig 15 Side view front view all dimensions in mm...
Page 28: ...Commissioning SCT5xxx 28 Version 1 0 Fig 18 Center conductors...
Page 32: ...Commissioning SCT5xxx 32 Version 1 0 Fig 21 SCT5xxx block diagram...
Page 40: ......