![Beckhoff SCJ6625 Manual Download Page 21](http://html1.mh-extra.com/html/beckhoff/scj6625/scj6625_manual_2719662021.webp)
Product overview
SCT6xxx
21
Version: 1.3
Split-core current transformers
Fig. 12: SCT6xxx
The separable measuring system of the SCT6xxx split-core current transformers enables flexible retrofitting
without disconnecting the primary conductor. Due to the minimal installation effort, they are suitable for use
in places that are difficult to access or where space is limited. Four sizes are available. Accuracy class 3 is
suitable for primary currents from 60 to 150 A, accuracy class 1 for 200 to 1000 A.
Split-core current transformers
Accuracy class 3,
Primary current 0...60 A AC to 0...150 A AC,
Secondary current 1 A AC,
Max. diameter round conductor 18.5 mm (size 1)
Accuracy class 1,
Primary current 0...200 A AC / 0...250 A AC,
Secondary current 1 A AC,
Max. diameter round conductor 18.5 mm (size 3)
Accuracy class 0.5,
Primary current 0...200 A AC / 0...250 A AC,
Secondary current 1 A AC,
Max. diameter round conductor 18.5 mm (size 3)
Accuracy class 1,
Primary current 0...300 A AC to 0...500 A AC,
Secondary current 1 A AC,
Max. diameter round conductor 27.9 mm (size 4)
Accuracy class 0.5,
Primary current 0...400 A AC / 0...500 A AC,
Secondary current 1 A AC,
Max. diameter round conductor 27.9 mm (size 4)
Accuracy class 1,
Primary current 0...600 A AC / 0...750 A AC,
Secondary current 5 A AC,
Max. diameter round conductor 42.4 mm (size 6)
Accuracy class 0.5,
Primary current 0...600 A AC / 0...750 A AC,
Secondary current 5 A AC,
Max. diameter round conductor 42.4 mm (size 6)
Accuracy class 1,
Primary current 0...800 A AC / 0...1000 A AC,
Secondary current 5 A AC,
Max. diameter round conductor 2 x 42.4 mm (size 7)
Accuracy class 0.5,
Primary current 0...800 A AC / 0...1000 A AC,
Secondary current 5 A AC,