Technical data, application notes, wiring
PS9031-4820-0001
23
1.0
4.18
Protective functions and safety features
Protective functions
Insulation resistance
> 500MOhm
In the delivery state between the mains power connection and sig-
nals, measured with 500 Vdc
> 500MOhm
In the delivery state between the mains power connection and the
housing, measured with 500 Vdc
> 500MOhm
In the delivery state between the signal connections and the hous-
ing, measured with 500 Vdc
PE resistance
< 0.1 ohm
Resistance between the chassis ground terminal and the housing.
Protection class
N/A
Install the buffer module according to the rules of Class III
Protection class / ingress protection
IP 20
EN/IEC 60529
Overtemperature protection
-
Output overvoltage protection
Typ. 58Vdc
Max. 60Vdc
In the event of a defect in the internal buffer module, a redundant
circuit limits the maximum output voltage. The buffering stops and
automatically attempts to restart.
Internal input fuse
-
Overvoltage protection at the input
Max. 60Vdc
Device not damaged or defective
Reverse polarity protection at the input Max. -60 Vdc
Device not damaged or defective
Touch current (leakage current)
The leakage current generated by the buffer module itself depends on the input voltage ripple
and must be investigated in the final application. With an even DC input voltage, the leakage
current generated is less than 100 μA.
4.19
Dielectric strength
The output voltage is earth-free and has no ohmic connection to earth.
Type and component tests are carried out by the manufacturer. Field tests can be performed in the field
using suitable test equipment that ramps up the voltage with a slow ramp (2s rising and 2s falling). Connect
all input terminals and all output poles to each other before performing the tests. During the test, set the cut-
off current to the value shown in the table below.
18: Dielectric strength
A
B
C
Type test
60s
500 Vac
500 Vac
500 Vac
Component test
5s
500 Vac
500 Vac
500 Vac
Field test
5s
500 Vac
500 Vac
500 Vac
Settings for the field test cut-off
current
> 1 mA
> 1 mA
> 1 mA