PS3011-4820-0000 Installation Manual 

 

 

 

Product Description 

The PS3011-4820-0000 is a DIN-rail mountable single-phase-input power supply, which provides a 
floating, stabilized and galvanically separated SELV/PELV output voltage. 
 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring and measurement equipment or the like.  
Do not use this device in equipment, where malfunctioning may cause severe personal injury or 
threaten human life without additional appropriate safety devices, that are suited for the end-
application. 
If this device is used in a manner outside of its specification, the protection provided by the device may 
be impaired. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. Other mounting orientations require a reduction in output current. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. Unused screw terminals 
should be securely tightened. Use ferrules for wires on the input terminals. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide 
protection against spilled liquids. 
The device is designed for overvoltage category II zones. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage 
between the input terminal and the PE potential must not exceed 276Vac. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 4000m (13125ft). Above 2000m (6560ft) a reduction in 
output current is required. 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 30A (UL) and 32A (IEC) without 
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 16A 
B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including unlimited inductive or capacitive loads. If capacitors with a capacitance >1F 
are connected, the unit might charge the capacitor in an intermittent mode. 
Do not apply return voltages from the load to the output terminals higher than 63V. 
The output voltage can be adjusted with a small flat-blade screwdriver behind the flap on the front. 
The DC OK LED reports an output voltage above 90% of the adjusted voltage of a running device. 
The DC OK relay monitors the output voltage and the contact is closed when the DC OK LED is on. 
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads. 
The red overload LED is on when the output voltage falls below 90% of the adjusted value. The LED is 
flashing, when the device is in overload or short circuit mode or has switched off due to over-
temperature or when the “Remote OFF” signal is activated. Input voltage is required. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
At heavy overloads (when output voltage falls below 40V), the device delivers continuous output 
current for 2 to 4s (depending on the overload). After this, the output is switched off for approximately 
17s before a new start attempt is automatically performed. This cycle is repeated as long as the 
overload exists. 
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to 
60°C. The output voltage of all devices shall be adjusted to the same value (±100mV) in 
“Single Use” mode with the same load conditions on all units, or the units can be left with the factory 
settings. After the adjustments, set the unit to “Parallel Use” mode, in order to achieve load sharing. 
The “Parallel Use” mode regulates the output voltage in such a manner that the voltage at no load is 
approx. 4% higher than at nominal load. Energize all units at the same time. It also might be 
necessary to cycle the input power (turn-off for at least five seconds), if the output was in overload or 
short circuit. If more than three devices are connected in parallel, a diode, fuse or circuit breaker with a 
rating of 30 or 32A is required on each output. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many 
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 60V. The output 
shuts down and automatically attempts to restart. 
The device is equipped with a remote ON/OFF function to turn the output off. For this connect pin 15 
with pin 16. 
The output voltage can be remotely adjusted between 44 and 54Vdc by applying a control voltage 
between pin 15 and the (-) terminal. See product datasheet for details. 

 

Technical Data

 

All values are typical figures specified at 230Vac 50Hz input voltage, 48V, 
20A output load, 25°C ambient temperature and after a 5 minutes run-in 
time unless otherwise noted. 

Output voltage 

DC 48V 

Nominal 

Adjustment range 

48 – 54Vdc 

Factory setting 24.1V 

Output current 

Continuous: 

 

20 – 17.8A 

Below +60°C ambient  

 

15 – 13.4A 

At +70°C ambient 

 

Short-term, up to 4s: 

 

30 – 26.7A 

Below +70°C ambient 

 

Derate linearly b60°C and +70°C 

Input voltage AC 

AC 100 - 240V 

-15% / +10% 

Mains frequency 

50 – 60Hz 

±6% 

Input current AC 

8.6 / 4.5A 

At 120 / 230Vac 

Power factor 

0.99 / 0.99 

At 120 / 230Vac 

Input inrush current 

17 / 11A pk 

At 120 / 230Vac, temp. 
independent 

Efficiency 

93.9 / 95.0% 

At 120 / 230Vac 

Power losses 

62.4 / 50.5W 

At 120 / 230Vac 

Hold-up time 

27 / 27ms 

At 120 / 230Vac 

Temperature range 

-25 to +70°C 

 

Max. wire size (litz wire) 

4mm² 

For input terminals 

Wire size AWG 

AWG 20-10 

For input terminals 

Max. wire diameter 

2.8mm 

For input terminals 

Wire stripping length 

7mm / 0.28inch 

For input terminals 

Tightening torque 

1Nm / 9lb.inch 

For input terminals 

Max. wire size (litz wire) 

10mm² For 

output 

terminals 

Wire size AWG 

AWG 22-8 

For output terminals 

Max. wire diameter 

5.2mm For 

output 

terminals 

Wire stripping length 

12mm / 0.5inch 

For output terminals 

Tightening torque 

2.3Nm / 20lb.inch For output terminals 

Max. wire size (litz wire) 

1.5mm² 

For signal terminals 

Wire size AWG 

AWG 26-14 

For signal terminals 

Max. wire diameter 

1.5mm 

For signal terminals 

Wire stripping length 

7mm / 0.28inch 

For signal terminals 

Size 

(wxhxd)

 

125x124x127mm Without 

DIN-rail 

Weight 

1900g / 4.2lb 

 

 

Functional Diagram 

+

+

-

-

Output

Over-

Voltage

Protection

Bridgeless

PFC

Converter

Voltage

Regulator

Power

Converter

Output

Filter

Output

Power

Manager

Temper-

ature

Shut-

down

Input Fuse
Input Filter
Inrush Current
Limiter

V

OUT

L

N

DC-OK

Contact

DC-OK

LED

DC-ok

Relay

13

14

Overload

LED

Single /

Parallel

Event Datalogger

ON/OFF,

Voltage

Control

15

16

Remote ON/OFF

Voltage control

 

Output Characteristic 

Output voltage

35A

48V

Output current

24V

0V

5A

15A

20A

25A

0A

Adjustment range

54V

A

B

10A

30A

C

40V

A: continuous current

B: intermittent current

C: up to 4s

 

Temperature Range 

Allowed output current at48V

Ambient temperature

0A

-25

30A

0

+70°C

15A

A

20A

60

A: continuous (90-264Vac)

B: continuous (85-90Vac)

C: up to 4s

55

C

B

 