background image

Technical data, mounting, wiring

PS2001-4810-0000

15

Version: 1.0

3.4

Output

The output provides an SELV/PELV/ES1 nominal voltage that is electrically isolated from the input voltage.

The device is designed to supply any type of load, including capacitive and inductive loads. If very large
capacitors, such as EDLCs (electrical double-layer capacitors or "UltraCaps") with a capacitance > 0.25F are
connected to the output, the device can charge the capacitor intermittently.

The output is electronically protected against overload, no-load and short circuit. In the event of a protection
event, audible noises may occur

Output voltage

Nom.

48V

Adjustment range

Min.

48-56V

Guaranteed value

Max.

60V

This is the maximum output voltage that can occur in the end position of the po-
tentiometer in clockwise direction due to tolerances. It is not a guaranteed
value that can be achieved.

Factory settings

Typ.

48.0V

±0.2%, single use at full load (cold device)

Typ.

47.0V

±0.2%, parallel use at 10A (cold device)
(46.6V ±0.2% at 12A and 49.0V ±0.2% at zero load)

Line regulation

Max.

10 mV

Between 85 and 300Vac

Load regulation

Max.

150 mV

Between 0 and 10A, static value, "single use"

Typ.

2000 mV

Between 0 and 10A, static value, "parallel use", see Fig. 

Output voltage over

output current (parallel use) typ.

Residual ripple and ripple
voltage

Max.

50mV

SS

Bandwidth 20 Hz to 20 MHz, 50 Ohm

Output current

Nom.

12A

1)

At 48 V and ambient temperature below 45°C

Nom.

10A

At 48 V and 60°C ambient temperature

Nom.

7.5A

At 48 V and 70°C ambient temperature

Nom.

10.3A

1)

At 56 V and ambient temperature below 45°C

Nom.

8.6A

At 56 V and 60°C ambient temperature

Nom.

6.5A

At 56 V and 70°C ambient temperature

Linear derating b45°C and +70°C

Safety 
switch-off current

Typ.

30A

Up to 12ms once every five seconds, see Fig. 

Dynamic output current capacity,

typ.

The fuse switch-off current is an increased transient current that contributes to
the tripping of fuses on faulty output branches. The output voltage remains
above 40V.

Overload behavior

Continuous cur-
rent

Output voltage > 26Vdc, see Fig. 

Output voltage over output current, typ

.

Hiccup mode 

2)

Output voltage < 26Vdc, see Fig. 

Output voltage over output current, typ.

Short circuit current

Max.

14.8A

Continuous current, see Fig. 

Output voltage over output current, typ.

Typ.

15A

Intermittent current peak value for typ. 2s
Load impedance 10mOhm, see Fig

. Short circuit at the output,

The discharge current of the output capacitors is not included.

max

4.7A

RMS value of the current,
Load impedance 10mOhm, see Fig. 

Short circuit at the output,

Output capacity

Typ.

2500μF

Included in the power supply

Load feedback

Max.

63V

The device is resistant to load feedback and will not indicate a malfunction if a
load is feeding voltage back into the power supply. It does not matter whether
the power supply is switched on or off. The absorbed energy can be deter-
mined by means of the built-in large-size output capacitor.

1)

 This current is also available for temperatures up to +70°C with a duty cycle of 10% and/or no more than 1

minute every 10 minutes.

2)

 In the event of heavy overload (when the output voltage drops below 13V), the power supply provides

continuous output current for 2s. The output is then switched off for about 18 seconds before a new switch-
on attempt is automatically made. This cycle is repeated as long as the overload persists. After the overload
has been rectified, the device will operate normally. See Fig. 

Short circuit at output, hiccup mode, typ.

Summary of Contents for PS2001-4810-0000

Page 1: ...Documentation EN PS2001 4810 0000 Power supply 48 V DC 10 A 1 phase 2020 10 08 Version 1 0...

Page 2: ......

Page 3: ...20 3 11 Functional wiring diagram 21 3 12 Front side and operating elements 22 3 13 EMC 23 3 14 Environment 24 3 15 Protective functions 25 3 16 Safety features 25 3 17 Dielectric strength 26 3 18 Dec...

Page 4: ...Table of contents PS2001 4810 0000 4 Version 1 0...

Page 5: ...with a continuous maximum output power of 120 and can precisely trigger fuses with a short peak current The power supply unit is part of the PS2000 family and has a width of 48 mm A DC OK LED and a po...

Page 6: ...are registered trademarks of and licensed by Beckhoff Automation GmbH Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the...

Page 7: ...device is designed for installation in a housing and is intended for general professional use for example in industrial control systems or office communication and measuring equipment Do not use this...

Page 8: ...r Do not touch the device when it is switched on or immediately after it has been switched off Hot sur faces can cause burns WARNING Explosion hazard warning Do not use with DC input voltages Do not u...

Page 9: ...the PE terminal must not exceed 300Vac continuously The input can also be powered from batteries or similar DC power sources The voltage between the input terminal and the PE terminal must not exceed...

Page 10: ...ith tolerances e g AC 230 V 10 The calculated total range then indicates the working range of the device Example DC 12 V refers to a 12 V battery regardless of whether it is fully charged 13 7 Vdc or...

Page 11: ...10A see Fig Input current over output current power factor over output current Power factor Typ 0 996 0 996 0 980 At 48V 10A see Fig Input current over output current power factor over output current...

Page 12: ...Technical data mounting wiring PS2001 4810 0000 12 Version 1 0 Fig 2 Input current over output current power factor over output current...

Page 13: ...ng to IEC 60664 1 Turn on voltage Typ 80 Vdc static Shut down voltage Typ 70 Vdc static Instructions for DC operation The device is suitable for supply from a DC input voltage Use a battery or a compa...

Page 14: ...tched on The charge current of the interference suppression capacitors during the first few microseconds after switching on is not taken into account AC 100V AC 120V AC 230V Input inrush current Max 1...

Page 15: ...nd 70 C ambient temperature Linear derating between 45 C and 70 C Safety switch off current Typ 30A Up to 12ms once every five seconds see Fig Dynamic output current capacity typ The fuse switch off c...

Page 16: ...fter a loss of input power The Hold up time depends on the output load At no load the Hold up time can be up to several seconds The green DC OK lamp also lights up during this time AC 100V AC 120V AC...

Page 17: ...voltage The contact opens when the output voltage drops more than 10 below the set output voltage Short drops are extended to a signal length of 100ms Drops that are shorter than 1ms are ignored Switc...

Page 18: ...W 10 6W At 48V 5A Typ 28 5W 25 1W 18 4W At 48V 10A Typ 35 4W 31 0W 22 7W At 48V 12A Extra Power The average efficiency is based on assumptions for a typical application with the power supply unit oper...

Page 19: ...MTBF MTBF stands for Mean Time Between Failure which is calculated from the statistical failure rate of the components and indicates the reliability of a device It is a statistical representation of t...

Page 20: ...ions Use suitable copper cables that are designed for at least the following operating temperatures 60 C for ambient temperatures up to 45 C 75 C for ambient temperatures up to 60 C and 90 C for ambie...

Page 21: ...Technical data mounting wiring PS2001 4810 0000 21 Version 1 0 3 11 Functional wiring diagram Fig 12 Functional wiring diagram...

Page 22: ...V DC OK LED Designation D Description LED green Lights when the output voltage has reached 90 of the set output voltage DC OK relay contact Designation E Description Push in terminals 13 14 Monitors t...

Page 23: ...0160 Over the entire load range 750V 0 3ms EMC interference emission Cable related interference emission input lines EN 55011 EN 55022 FCC Part 15 CISPR 11 CISPR 22 Class B Interference emission EN 55...

Page 24: ...altitudes up to 2000m II According to IEC 60664 1 installation altitudes above 2000m Degree of pollution 2 According to IEC 62477 1 non conductive Oscillation sinusoidal 2 2 17 8Hz 1 6mm 17 8 500Hz 2...

Page 25: ...ction against input transients MOV metal oxide varis tor For further information see EMC chapter 23 Input fuse Included Non replaceable slow blow fuse with high load capacity 3 16 Safety features Safe...

Page 26: ...current to the value shown in the table below We recommend connecting either the positive pole the negative pole or another part of the output circuit to the protective conductor system This avoids s...

Page 27: ...on of conformity UL Certificate UL 61010 1 2 201 Applicable for US and Canada UL Certificate Class I Division 2 Groups A B C D locations and for use in Group II Category 3 Zone 2 environments Applicab...

Page 28: ...ulate the total installation depth required Weight 830 g DIN rail Use 35 mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm Housing material Housing Aluminum alloy Cover Galva...

Page 29: ...citive load The peak current capability also ensures safe operation of downstream circuit breakers of load circuits The load circuits are often individually fused with circuit breakers or fuses In the...

Page 30: ...t Control of DC OK relay Please note The DC OK relay is activated if the voltage drops by more than 10 for more than 1ms Peak current voltage drops Typically from 48V to 36V At 20A for 50ms ohmic load...

Page 31: ...s with high reserve current and large output capacitors In addition the impedance of the faulty branch must be sufficiently small for the current to actually flow The strongest power supply is of no u...

Page 32: ...ies connection Power supplies of the same type can be connected in series to increase the output voltages As many devices can be connected in series as necessary as long as the sum of the output volta...

Page 33: ...up and shut down the input power turn off for at least five seconds if the output was overloaded or short circuited and the required output current is higher than the current of a device Restrictions...

Page 34: ...heat generating objects in the box The load is placed outside the enclosure The temperature sensor inside the enclosure is placed at the center of the right side of the power supply at a distance of...

Page 35: ...permissible output currents for altitudes up to 2000m Fig 24 Mounting position A standard mounting position Fig 25 Mounting position B upside down Fig 26 Mounting position C table mounting Fig 27 Mou...

Page 36: ...devices to a wall or panel without using a DIN rail The bracket can be mounted without loosening the DIN rail brackets For more information please refer to the ZS5301 0003 documentation Fig 29 Isomet...

Page 37: ...Appendix PS2001 4810 0000 37 Version 1 0 5 2 Documentation issue status Version Comment 1 0 First public issue 0 2 Complements corrections 0 1 Preliminary documentation for PS2001 4810 0000...

Page 38: ...khoff components there Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wide ranging...

Page 39: ......

Page 40: ...Beckhoff Automation GmbH Co KG H lshorstweg 20 33415 Verl Germany Phone 49 5246 9630 info beckhoff com www beckhoff com More Information www beckhoff com ps2001 4810 0000...

Reviews: