Technical data, mounting, wiring
PS1111-2403-0002
10
Version: 1.0
3
Technical data, mounting, wiring
3.1
AC input
AC input
AC input
Nom.
AC 100-240V
Suitable for TN, TT and IT networks
AC input range
Min.
90-264Vac
Continuous operation
Min.
264-300Vac
For up to 500 ms max.
Permissible voltage L or N to earth Max.
300Vac
Continuous according to IEC 60664-1
Input frequency
Nom.
50-60Hz
±6%
Turn-on voltage
Typ.
75Vac
Static, see Fig.
Input voltage range
Shut-down voltage
Typ.
54Vac
Static, see Fig.
Input voltage range
External input protection
See recommendations in chapter
Safety and installation requirements [
AC input
AC100V
AC120V
AC230V
Input current
Typ.
1.69A
1.45A
0.95A
At 24V, 3.8A, see Fig.
Input current over output current;
Power factor
Typ.
0.6
0.58
0.45
At 24V, 3.8A, see Fig.
Power factor over output current
Start-up delay
Typ.
50ms
50ms
50ms
See Fig.
Switch-on behavior definitions
Rise time
Typ.
21ms
21ms
20ms
At 24V, 3.8A constant current load, 0mF load capaci-
tance, see Fig.
Switch-on behavior definitions
Typ.
42ms
42ms
40ms
At 24V, 3.8A constant current load, 2mF load capaci-
tance, see Fig.
Switch-on behavior definitions
Turn-on overshoot
Max.
100 mV
100 mV
100 mV
See Fig.
Switch-on behavior definitions
Fig. 1: Input voltage range; switch-on behavior definitions