Technical data, mounting, wiring
PS1111-2402-0002
10
Version: 1.0
3
Technical data, mounting, wiring
3.1
AC input
AC input
AC input
Nom.
AC 100-240V
Suitable for TN, TT and IT networks
AC input range
Min.
90-264Vac
Continuous operation
Min.
264-300Vac
For up to 500 ms max.
Permissible voltage L or N to earth Max.
300Vac
Continuous according to IEC 60664-1
Input frequency
Nom.
50-60Hz
±6%
Turn-on voltage
typ.
75Vac
Static, see Fig. Input voltage range; switch-on behavior definitions
Shut-down voltage
typ.
54Vac
Static, see Fig. Input voltage range; switch-on behavior definitions
External input protection
See recommendations in chapter
Safety instructions and installation requirements [
AC input
AC 100V
AC120V
AC230V
Input current
typ.
1.15A
1.0A
0.60A
At 24 V, 2.5 A, see Fig.
Input current over out-
put current; power factor over output current
Power factor*)
typ.
0.58
0.55
0.47
At 24 V, 2.5 A, see Fig.
Input current over out-
put current; power factor over output current
Start-up delay
typ.
50ms
50ms
48ms
See Fig.
Input voltage range; switch-on behav-
ior definitions
Rise time
typ.
18ms
18ms
18ms
At 24 V, 2.5 A constant current load, 0 mF load
capacity, see
Fig. Input voltage range; switch-
on behavior definitions
typ.
52ms
52ms
50ms
At 24 V, 2.5 A constant current load, 2 mF load
capacity, see Fig.
Input voltage range; switch-
on behavior definitions
Turn-on overshoot
Max.
100 mV
100 mV
100 mV
See Fig.
Input voltage range; switch-on behav-
ior definitions
*) The power factor is the ratio of real (or active) power to apparent power in an AC circuit.
Fig. 1: Input voltage range; switch-on behavior definitions