Technical data, mounting, wiring
PS1011-2410-0000
18
Version: 1.0
3.9
Terminals and wiring
The terminals are designed to be finger-safe according to IP20 and are suitable for field or factory wiring.
Technical data
Input
Output
DC-OK signal
Connection cross-section
e*: max. 6mm²
f*: max. 4mm²
a*: max. 4mm² (d<2.8mm)
e*: max. 6mm²
f*: max. 4mm²
a*: max 4mm² (d<2.8mm)
e*: max. 1.5mm²
f*: max. 1.5mm²
a*: max. 1.5mm²
(d<1.6mm)
Connection cross section
(AWG)
e*: AWG 20-10
f*: AWG 20-10
a* AWG 20-10 (d<2.8mm)
e*: AWG 20-10
f*: AWG 20-10
a* AWG 20-10
(d<2.8mm)
e*: AWG 28-16
f*: AWG 28-16
a*: AWG 28-16
(d<1.6 mm)
Strip length
7mm / 0.28inch
7mm / 0.28inch
7mm / 0.28inch
e* = solid wire
f* = stranded wire
a* = with ferrule
Instructions
• Use suitable copper cables that are designed for a minimum operating temperature of:
- 75°C for ambient temperatures up to 55°C and
- 90°C for ambient temperatures up to at least 70°C.
• Observe national installation rules and regulations!
• Make sure all individual wires of a strand enter the terminal connection!
• Do not use the device without PE connection.
• Unused terminal spaces should be tightened securely.
• Ferrules are permissible.