Product overview
KM3701, KM3702 and KM3712
11
Version: 2.0.0
2.4
Technical data
Technical Data
KM3701-0000
KM3701-0340
KM3702-0000
KM3712-0000
Number of inputs
1 (differential pressure)
2
2
Measuring range
-100 to +100 hPa
(-100 to +100 mbar)
-340 to +340 hPa
(-340 to
+340 mbar)
0 to 7500 hPa
(0 to 7.5 bar)
-1000 to +1000 hPa
(-1 to +1 bar)
Permissible overpressure
max. ±500 hPa differential
max. +5000 hPa relative to ambient
+10000 hPa
+5000 hPa
permissible media
non-aggressive gases
Resolution
0.1 hPa (0.1 mbar) per digit
1 hPa (1 mbar)
per digit
1 hPa (1 mbar) per
digit
Measuring accuracy
3% (of the full scale value)
Measuring speed
typically 5 ms
Pressure connectors
Power supply for the
electronics
via the K-bus
Current consumption from
the K-bus
typically 15 mA
Width of a bus terminal
block
Maximum 64 standard Bus Terminals or 80 cm
(a KM37xx is equivalent to 2 standard Bus Terminals)
Electrical isolation
500 V (K-bus/signal voltage)
Bit width in the input
process image
3 byte
3 byte
6 byte
6 byte
Bit width in the output
process image
3 byte
3 byte
6 byte
6 byte
Dimensions without tubes
(w x h x d)
approx. 26.5 mm x 100 mm x 69 mm (width aligned: 24 mm)
Weight
approx. 100 g
Permissible ambient
temperature range during
operation
0°C ... + 55°C
Permissible ambient
temperature range during
storage
-25°C ... + 85°C
Permissible relative air
humidity
95 %, no condensation
on a 35 mm
(e.g. DIN rail TH 35-7.5 conforming to EN
60715)
Vibration / shock
resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE, cULus