![Beckhoff KL9020 Documentation Download Page 12](http://html1.mh-extra.com/html/beckhoff/kl9020/kl9020_documentation_2719271012.webp)
Product Overview
KL9020, KL9050
12
Version: 2.1.0
2.3
KL9050: Coupler Terminal
Fig. 4: KL9050
LED
No.
Function
Power V
k
, green
A
LED indicates whether the supply voltage for the electronics of the Coupler Terminal is switched on.
Power, green
C
LED indicates whether the supply voltage for the I/O terminals of the terminal block is switched on. The
power supply of the terminals is via the power contacts.
RUN (K-Bus IN), green
-
LED indicates that data is being transmitted on the K-bus.
ERR (K-Bus IN), red
-
LED indicating a fault on the K-Bus.
Terminal point
No.
Function
V
k
24 V
1
Input of the +24 V supply voltage for the Coupler Terminal electronics
+24 V
2
Input of the +24 V supply voltage for the power contacts (internally connected to terminal point 6)
0 V
3
Input of the 0 V supply voltage for the power contacts (internally connected to terminal point 7)
PE
4
PE connection (internally connected to terminal point 8)
V
k
0 V
5
Input of the 0 V supply voltage for the Coupler Terminal electronics
+24 V
6
Input of the +24 V supply voltage for the power contacts (internally connected to terminal point 2)
0 V
7
Input of the 0 V supply voltage for the power contacts (internally connected to terminal point 3)
PE
8
PE connection (internally connected to terminal point 4)
Interface
Function
K-bus In
RJ45 socket for the incoming K-bus extension
K-bus OUT
RJ45 socket for the continuing K-bus extension
K-bus
Internal K-bus of the Bus Terminal block
Power Contacts
Internal power contacts of a bus terminal block
Switch for the termination resistor of the Coupler Terminal