KS2000 Configuration Software
KL3403
43
Version: 3.1.0
deletion time (R38 [
Here you can change the time constant (resolution: 10 ms) for automatic deletion of the minimum and
maximum current, voltage and power values (default: 2000 ms).
Password
Here you change can the password for the KL3403 (default: 4661
dec
), in order to prevent unauthorized
deletion of the energy consumption:
• Enter the old password in the field at the top.
• Enter the new password in the field in the center.
• Repeat the new password in the field at the bottom and click
Change password
Password
In this dialog box, you have to enter the passwords in decimal form! You can also use the password
change register (
) to change the password.
Energy consumption
Here you can clear the stored energy consumption. Enter the password and click
Delete
.
Deleting the energy consumption
Once the energy consumption has been deleted, the value cannot be restored!
4.4
Sample program for KL register communication via
EtherCAT on KL3314 exemplary
Using the sample programs
This document contains sample applications of our products for certain areas of application. The
application notes provided here are based on typical features of our products and only serve as ex-
amples. The notes contained in this document explicitly do not refer to specific applications. The
customer is therefore responsible for assessing and deciding whether the product is suitable for a
particular application. We accept no responsibility for the completeness and correctness of the
source code contained in this document. We reserve the right to modify the content of this docu-
ment at any time and accept no responsibility for errors and missing information.
Program description / function
This example program (TwinCAT 3) provides change of single register values of the KL3314 as selection of
the element type, characteristical settings of the feature register R32 and user scaling offset and gain (R33/
R34) similar as per KS2000.