Product overview
KL3224
11
Version: 2.0.0
2.2
Technical data
Technical data
KL3224
Number of inputs
4
Power supply
via the K-bus
Sensor types
PT1000, Ni1000
Connection technology
2-wire
Temperature range
0 °C ... +40 °C
Resolution
0.1 °C per digit
Electrical isolation
500 V (K-bus / signal voltage)
Conversion time
approx. 250 ms
Measuring current
typically 0.5 mA.
Measuring error (total meas.
range)
< ± 1 °C (at 0 °C ... +55 °C)
Bit width in process image
Input: 4 x 16 bits of data (4 x 8 bit control/status optional)
Current consumption via K-bus
typically 60 mA
Configuration
no address setting, configuration via bus coupler or controller
Special features
Open-circuit recognition
Weight
approx. 70 g
Permissible ambient temperature
during operation
0 °C ... +55 °C
Permissible ambient temperature
during storage
-25 °C ... +85 °C
Permissible relative humidity
95% no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
variable
Protection class
IP20
Approval / identification
CE
2.3
Basic function principles
Process data output format
In the delivery state, the measured value is displayed in increments of 1/10 °C in two's complement format
(integer). The complete measuring range is output for each resistance sensor. Other presentation types can
be selected via the feature register (e.g., signed amount representation, Siemens output format).
Measured value
Hexadecimal output
Signed integer output
-250.0 °C
0xF63C
-2500
-200.0 °C
0xF830
-2000
-100.0 °C
0xFC18
-1000
-0.1 °C
0xFFFF
-1
0.0 °C
0x0000
0
0.1 °C
0x0001
1
100.0 °C
0x03E8
1000
200.0 °C
0x07D0
2000
500.0 °C
0x1388
5000
850.0 °C
0x2134
8500