Access from the user program
KL3222
34
Version: 2.3.0
5.2.2
Register communication
Control byte 1 (in register communication)
Control byte 1 (CB1) is located in the output image, and is transmitted from the controller to the terminal.
Bit
CB1.7
CB1.6
CB1.5
CB1.4
CB1.3
CB1.2
CB1.1
CB1.0
Name
RegAccess R/W
Reg. no.
Key
Bit
Name
Description
CB1.7
RegAccess 1
bin
Register communication switched on
CB1.6
R/W
0
bin
Read access
1
bin
Write access
CB1.5 to
CB1.0
Reg. no.
Register number:
Enter the number of the
that you
- want to read with input data word
or
- want to write with output data word
Status byte 1 (in register communication)
The status byte 1 (SB1) is located in the input image and is transmitted from terminal to the controller.
Bit
SB1.7
SB1.6
SB1.5
SB1.4
SB1.3
SB1.2
SB1.1
SB1.0
Name
RegAccess R/W
Reg. no.
Key
Bit
Name
Description
SB1.7
RegAccess 1
bin
Acknowledgment for register access
SB1.6
R
0
bin
Read access
SB1.5 to
SB1.0
Reg. no.
Number of the register that was read or written.
Summary of Contents for KL3222