Access from the user program
KL301x, KL302x
34
Version: 4.1
Default mapping for: Profibus and Interbus Coupler
Conditions
Word offset
High byte
Low byte
Complete evaluation: no
Motorola format: yes
Word alignment: any
0
Ch1 D0
Ch1 D1
1
Ch2 D0
Ch2 D1
2
-
-
3
-
-
Conditions
Word offset
High byte
Low byte
Complete evaluation: yes
Motorola format: no
Word alignment: no
0
Ch1 D0
Ch1 CB/SB
1
Ch2 CB/SB
Ch1 D1
2
Ch2 D1
Ch2 D0
3
-
-
Conditions
Word offset
High byte
Low byte
Complete evaluation: yes
Motorola format: yes
Word alignment: no
0
Ch1 D1
Ch1 CB/SB
1
Ch2 CB/SB
Ch1 D0
2
Ch2 D0
Ch2 D1
3
-
-
Default mapping for: Lightbus & Ethernet coupler and Bus Terminal Controller (BCxxxx, BXxxxx)
Conditions
Word offset
High byte
Low byte
Complete evaluation: yes
Motorola format: no
Word alignment: yes
0
Res.
Ch1 CB/SB
1
Ch1 D1
Ch1 D0
2
Res.
Ch2 CB/SB
3
Ch2 D1
Ch2 D0
Conditions
Word offset
High byte
Low byte
Complete evaluation: yes
Motorola format: yes
Word alignment: yes
0
Res.
Ch1 CB/SB
1
Ch1 D0
Ch1 D1
2
Res.
Ch2 CB/SB
3
Ch2 D0
Ch2 D1
Key
Complete evaluation
The terminal is mapped with control and status byte.
Motorola format
Motorola or Intel format can be set.
Word alignment
The terminal is positioned on a word boundary in the Bus Coupler.
Ch n CB
Control byte for channel n (appears in the process image of the outputs).
Ch n SB
Status byte for channel n (appears in the process image of the inputs).
Ch n D0
Channel n, data byte 0 (byte with the lowest value)
Ch n D1
Channel n, data byte 1 (byte with the highest value)
"-"
This byte is not used or occupied by the terminal.
Res.
Reserved: This byte is assigned to the process data memory, although it has no function.
5.3
Register overview
These registers exist once for each channel.