Product overview
EPI4xxx, ERI4xxx
10
Version: 1.6
2.2.2
Technical data
All values are typical values over the entire temperature range, unless stated otherwise.
IO-Link
Connection
1 x M12 plug, 5-pin, A-coded
Data transfer rate
230.4 kbaud (COM 3)
Specification version
IO-Link V1.1, Class B
Requirements for IO-Link master
V1.1
Current consumption from L+
100 mA
Current consumption from P24
Current for sensor supply
Current for actuator supply
Electrical isolation L+ / P24
yes
Analog inputs
Number
2
Connection
2 x M12 socket, 5-pin
Input type
Differential
Measuring range
Adjustable:
• -10 … +10 V (factory setting)
• 0 … 10 V
• 0 … 20 mA
• 4 … 20 mA
Specifications of the measuring ranges [
Sensor supply
24 V
DC
from P24, not short-circuit proof
Analog outputs
Number
2
Connection
2 x M12 socket, 5-pin
Output signal range
Adjustable:
• -10 … +10 V (factory setting)
• 0 … 10 V
• 0 … 20 mA
• 4 … 20 mA
Specifications of the output signal ranges [
Actuator supply
24 V
DC
from P24, not short-circuit proof
Housing data
EPI4374-0002
ERI4374-0002
Dimensions W x H x D
30 mm x 126 mm x 26.5 mm (without plug connectors)
Weight
approx. 165 g
approx. 250 g
Installation position
variable
Material
PA6 (polyamide)
Die-cast zinc