Index 0800 AI Settings Ch.1 (parameterization of channel 1)
Index
(hex)
Name
Meaning
Data type
Flags
Default
0800:00
AI Settings Ch1
Maximum subindex
UINT8
RO
0x18 (24
dec
)
0800:01
Enable User Scale
1
User scale is active.
BOOLEAN
RW
0x00 (0
dec
)
0800:02
Presentation
0
Signed presentation (default)
UINT3
RW
0x00 (0
dec
)
1
Unsigned presentation
2
Absolute value with MSB as sign (signed
amount representation)
0800:05
Siemens bits
1
Status indicators are displayed on the
lowest 3 bits in the status word.
BOOLEAN
RW
0x00 (0
dec
)
0800:06
Enable filter
1
Enable filter, which makes PLC-cycle-
synchronous data exchange unnecessary
BOOLEAN
RW
0x01 (1
dec
)
0800:07
Enable Limit 1
1
Limit 1 enabled
BOOLEAN
RW
0x00 (0
dec
)
0800:08
Enable Limit 2
1
Limit 2 enabled
BOOLEAN
RW
0x00 (0
dec
)
0800:0A
Enable User Calibration
1
Enabling of the user calibration
BOOLEAN
RW
0x00 (0
dec
)
0800:0B
Enable Vendor Calibration
1
Enabling of the vendor calibration
BOOLEAN
RW
0x01 (1
dec
)
0800:0E
Swap Limit Bits
1
Swaps the two limit bits, in order to
achieve compatibility with older hardware
versions.
BOOLEAN
RW
0x00 (0
dec
)
0800:11
User Scale Offset
User scale offset
INT16
RW
0x0000 (0
dec
)
0800:12
User Scale Gain
User scale gain.
The gain is represented in fixed-point format,
with the factor 2
-16
.
The value 1 corresponds to 65535
dec
(0x00010000
hex
) and is limited to +/- 0x7FFFF
INT32
RW
0x00010000
(65536
dec
)
0800:13
Limit 1
First limit value for setting the status bits
INT16
RW
0x0000 (0
dec
)
0800:14
Limit 2
Second limit value for setting the status bits
INT16
RW
0x0000 (0
dec
)
0800:15
Filter Settings
This object determines the digital filter set-
tings
for all channels of the module
, if it is
activated via Enable filter (index 0x80n0:06).
The possible settings are sequentially num-
bered.
UINT16
RW
0x0000 (0
dec
)
0
50 Hz FIR
1
60 Hz FIR
2
IIR 1
3
IIR 2
4
IIR 3
5
IIR 4
6
IIR 5
7
IIR 6
8
IIR 7
9
IIR 8
0800:17
User Calibration Offset
User calibration: Offset
INT16
RW
0x0000 (0
dec
)
0800:18
User Calibration Gain
User calibration: Gain
INT16
RW
0x4000 (16384
dec
)
Index 080E ADC raw value
Index
(hex)
Name
Meaning
Data type
Flags
Default
080E:01
ADC raw value
Raw value of the analog/digital converter
INT16
RO
0x0000 (0
dec
)
Index 080F Al vendor data Ch1
Index
(hex)
Name
Meaning
Data type
Flags
Default
080F:0
Al Vendor data Ch1
Maximum subindex
RO
0x0C (12
dec
)
080F:01
R0 offset
Offset (vendor calibration)
INT16
RW
0x0000 (0
dec
)
08 F:02
R0 gain
Gain (vendor calibration)
INT16
RW
0x4000 (16384
dec
)
080F:03
R1 offset
Offset (vendor calibration)
INT16
RW
0x0000 (0
dec
)
080F:04
R1 gain
Gain (vendor calibration)
INT16
RW
0x4000 (16384
dec
)
080F:05
R2 offset
Offset (vendor calibration)
INT16
RW
0x0000 (0
dec
)
080F:06
R2 gain
Gain (vendor calibration)
INT16
RW
0x4000 (16384
dec
)