Error handling und diagnosis
EP9300-0022
55
Version: 2.3
8
Error handling und diagnosis
8.1
LED display
EtherCAT Link/Act
Profinet status
Profinet Link/Act
Supply voltage status
EtherCAT Link/Act
LED
Display
Meaning
Link/Act
off
No connection to the following EtherCAT module.
green illuminated
Link: connection to the following EtherCAT module.
green flashing
Act: Communication with the following EtherCAT module.
Profinet status
LED
Display
Meaning
RUN
green illuminated
EP9300-0022 is ready.
red illuminated
May only light up during the start-up phase
PN
red flashing (200 ms)
Start-up phase
green flashing
(200 ms)
green flashing
(1 s off, 200 ms on)
green illuminated
OK
DIAG
red/green flashing
(500 ms)
Profinet controller identification:
The Profinet controller is transmitting an identification signal.
red flashing
(200 ms)
No AR established:
The establishment of a connection with the controller has not been
completed.
green flashing
(1 s off, 200 ms on)
Problem with establishment of a connection or nominal and actual
configuration differ.
green flashing (200 ms)
EP9300-0022 is in data exchange, but PLC is in stop
green illuminated
OK