Product overwiew
ELX2002 and ELX2008
14
Version: 2.0.0
2.3
Technical data
Technical data
ELX2002-0000
ELX2008-0000
Technology
intrinsically safe actuators
Number of outputs
2
8
Connection technology
2-wire
Rated load voltage
24 V
DC
(RI = 254 Ω)
24 V
DC
(RI = 272 Ω)
Output current
45 mA per channel, ∑ 80 mA
30 mA per channel
Load type
ohmic, inductive, capacitive
Supply voltage electronics
via E-Bus (5 V
DC
) and power contacts (24 V
DC
Ex, feeding by
ELX9560)
Current consumption from the E-Bus
typical 45 mA
Current consumption from power contacts
typical 10 mA + load
typical 30 mA + load
Electrical isolation
1500 V (E-Bus / field voltage)
Configuration
no address or configuration setting
Bit width in the process image
2 x 1 bit
2 x 8 bit
Weight
app. 55 g
app. 100 g
Dimensions (W x H x D)
app. 15 mm x 100 mm x
70 mm (width aligned: 12 mm)
app. 27 mm x 100 mm x
70 mm (width aligned: 24 mm)
Permissible ambient temperature range
during operation
-25°C ... + 60°C
Permissible ambient temperature range
during storage
-40°C ... + 85°C
Permissible relative humidity
95%, no condensation
Permissible air pressure
(operation, storage, transport)
800 hPa to 1100 hPa
(this corresponds to a height of approx. -690 m to 2000 m
over sea level assuming an international standard
atmosphere)
Mounting
on 35 mm mounting rail conforms to EN 60715
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protect. class
IP20
Permissible installation position
Installation position and minimum distances
Approvals / markings
CE, UL, ATEX, IECEx, cFMus CE, ATEX, IECEx
Summary of Contents for ELX2002
Page 2: ......
Page 4: ...Table of contents ELX2002 and ELX2008 4 Version 2 0 0...