Product overview
ELX4154
13
Version: 1.0
2.2
Technical data
Technical data
ELX4154-0000
Technology
intrinsically safe sensors
Number of outputs
4 (single ended)
Connection technology
2-wire
Nominal voltage
24 V
DC
Signal current
0/4…20 mA
Load
400 Ω
Resolution
16 bit (incl. sign)
Conversion time
typically 1 ms
Supply voltage electronics
via E-Bus (5 V
DC
) and Power Contacts (24 V
DC
Ex, feeding
by ELX9560)
Current consumption from the E-Bus
typically 60 mA
Current consumption from Power Contacts
typically 21 mA + 0.8 x load (ELX9560 power supply)
Electrical isolation
1500 V (E-Bus / field voltage)
Configuration
no address or configuration settings required
Distributed Clocks
yes
Bit width in the process image
4 x 2 byte
Special features
Watchdog parameterizable
User scaling can be activated
Weight
app. 100 g
Permissible ambient temperature range during
operation
-25°C ... + 60°C
Permissible ambient temperature range during
storage
-40°C ... + 85°C
Permissible relative humidity
95%, no condensation
Permissible air pressure
(operation, storage, transport)
800 hPa to 1100 hPa
(this corresponds to a height of approx. -690 m to 2000 m
over sea level assuming an international standard
atmosphere)
Dimensions (W x H x D)
app. 27 mm x 100 mm x 70 mm (width aligned: 24 mm)
Mounting
on 35 mm mounting rail conforms to EN 60715
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protect. class
IP20
Permissible installation position
See chapter
Installation position and minimum distances
Approvals / markings
CE, ATEX, IECEx