Product description
EL2904
18
Version: 2.3.0
3.3
Technical data
Product designation
EL2904
Number of outputs
4
Status display
4 (one green LED per output)
Fault reaction time
≤ watchdog times
Output current per channel
max. 500 mA, min. 20 mA with
Current Measurement Active
pa-
rameter enabled
Utilization category according to EN 60947-5-1
DC-13
Intended load
Pilot Duty
Actuators
When selecting actuators please ensure that the EL2904 test
pulses do not lead to actuator switching.
Cable length between actuator and terminal
unshielded max. 100 m
shielded max. 100 m
Wire cross-section
min. 0.75 mm
2
Input process image
6 bytes
Output process image
6 bytes
EL2904 supply voltage (PELV)
24 V
DC
(–15% / +20%)
(A 10 A fuse should be provided for the potential group)
Protection class
III
(by using a SELV/PELV power supply unit)
Overvoltage category
II
Current consumption via E-bus
approx. 221 mA
Power dissipation of the terminal
typically 2 W
Electrical isolation (between the channels)
no
Electrical isolation (between the channels and the E-bus)
yes
Insulation voltage (between the channels and the E-bus, under com-
mon operating conditions)
Insulation tested with 500 V
DC
Dimensions (W x H x D)
24 mm x 100 mm x 68 mm
Weight
approx. 100 g
Permissible ambient temperature (operation)
up to SW 03
0°C to +55°C (see notes in chapter Example configuration for
temperature measurement)
Permissible ambient temperature (operation)
from SW 04 (CW 02/2014)
-25°C to +55°C (see notes in section Example configuration for
temperature measurement)
Permissible ambient temperature (transport/storage)
-40 °C to +70 °C
Permissible air humidity
5% to 95%, non-condensing
Permissible air pressure (operation/storage/transport)
750 hPa to 1100 hPa
(this corresponds to an altitude of approx. -690 m to 2450 m
above sea level, assuming an international standard atmos-
phere)
Climate category according to EN 60721-3-3
3K3
(the deviation from 3K3 is possible only with optimal environmen-
tal conditions and also applies only to the technical data which
are specified differently in this documentation)
Permissible pollution degree
according to EN 60664-1
Inadmissible operating conditions
TwinSAFE Terminals must not be used under the following oper-
ating conditions:
• under the influence of ionizing radiation (exceeding the
natural background radiation)
• in corrosive environments
• in an environment that leads to unacceptable soiling of
the Bus Terminal
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
Shocks
15 g with pulse duration 11 ms in all three axes
Protection class
IP20
Equipment type according to EN 61010-2-201
Open equipment
Permitted operating environment
In the control cabinet or terminal box, with minimum protection
class IP54 according to IEC 60529
Correct installation position
see chapter Installation position and minimum distances
Approvals
CE, cULus, ATEX, TÜV SÜD
Summary of Contents for EL2904
Page 2: ......
Page 8: ...Foreword EL2904 8 Version 2 3 0 1 3 Documentation issue status ...
Page 36: ...Operation EL2904 36 Version 2 3 0 Fig 19 Inserting an EL2904 ...
Page 47: ...Appendix EL2904 47 Version 2 3 0 5 2 Certificates ...
Page 48: ...Appendix EL2904 48 Version 2 3 0 ...
Page 50: ......