![Beckhoff EK1122 Documentation Download Page 16](http://html1.mh-extra.com/html/beckhoff/ek1122/ek1122_documentation_2719480016.webp)
Product overview
EK1122, EK15xx
16
Version: 3.4
3.1.1.2
Technical data
Technical data
EK1122
EK1122-0080
Task within the EtherCAT system
Coupling of EtherCAT junctions
Coupling of EtherCAT junctions,
Transmission medium
Ethernet 100BASE-TX (min. CAT5)
Cable length between two Bus Couplers max. 100 m
Protocol / Baud rate
EtherCAT/ 100 Mbaud
Configuration
no address and configuration settings required
Bus connection
2 x RJ45
Power supply
from E-bus
Current consumption
typ. 220 mA
Dimensions (W x H x D)
approx. 26 mm x 100 mm x 52 mm (width aligned: 23 mm)
Weight
approx. 70 g
Permissible ambient temperature range
during operation
-25°C ... +60°C
(extended temperature range)
Permissible ambient temperature range
during storage
-40°C ... + 85°C
Permissible relative humidity
95%, no condensation
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE
3.1.1.3
Notes re. EtherCAT Fast Hot Connect technology
EtherCAT components that support Fast Hot Connect enable a faster fieldbus boot up following the
establishment of a connection. The boot up depends in detail on the number of devices, the topology and
activated Distributed Clocks. Whereas the normal establishment of a connection and communication takes
several seconds, less than 1 second is possible with FHC components.
Properties and system behavior
• Fast Hot Connect is supported from TwinCAT 2.11R3 Build 2221.
• Fast Hot Connect ports are specially marked.