EJ4002, EJ4004, EJ4008 - Technical Data
Technical data
EJ4002
EJ4004
EJ4008
Number of outputs
2
4
8
Power supply
24 V
DC
via Up contacts
Signal voltage
0 V .. 10 V
Distributed Clocks
yes
Load
> 5 kΩ (short-circuit-proof)
Measuring error
< 0.1 % (at 0°C…+55°C, rel-
ative to full scale value)
< ±0.2% (when using the ex-
tended temperature range,
relative to the full scale
value)
< 0.1 % (relative to full scale value)
Resolution
12-bit
Electrical isolation
500 V (E-bus/signal voltage)
Conversion time
~ 150 µs
~ 400 µs
Current consumption load voltage (Up con-
tacts)
typ. 20 mA
typ. 25 mA
Current consumption via E-bus
typ. 90 mA
Permissible ambient temperature range
during operation
-25 °C .. +60 °C (extended
temperature range)
0 °C .. +55 °C
Permissible ambient temperature range
during storage
-40 °C .. +85 °C
-25 °C .. +85 °C
Permissible relative air humidity
95 %, no condensation
Operating altitude
max. 2,000 m
Dimensions (W x H x D)
approx. 12 mm x 66 mm x 55 mm
Weight
approx. 30 g
Mounting
on signal distribution board
Mounting position
Pollution degree
2
1 and 7
Color coding
blue
Vibration / shock resistance
conforms to EN 60068-2-6 /EN 60068-2-27 (with corresponding signal distribution board)
EMC immunity / emission
conforms to EN 61000-6-2 /EN 61000-6-4 (with corresponding signal distribution board)
Protection class
EJ module: IP20
EJ system: dependent on the signal distribution board and housing
Approval
CE, UL
CE
CE approval
The CE Marking refers to the EtherCAT plug-in module mentioned above.
If the EtherCAT plug-in module is used in the production of a ready-to-use end product (PCB in con-
junction with a housing), the manufacturer of the end product must check compliance of the overall
system with relevant directives and CE certification.
To operate the EtherCAT plug-in modules, they must be installed in a housing.