Configuration
CX51x0
54
Version: 2.8
• The serial interfaces are displayed in the Windows Device Manager as COM1 interfaces.
In the following, we show you how to change the BIOS settings in order to use the serial interfaces with
Windows 10.
Set the BIOS as follows in order to operate the serial interfaces with Windows 10:
1. Start the Embedded PC and press
[Del]
to open the BIOS setup.
The BIOS setup window appears.
2. Under
Advanced > LPSS & SCC Configuration
, set the option
LPSS & SCC Devices Mode
to
ACPI
mode
.
3. Under
Advanced > Miscellaneous Configuration
, set the option
OS Selection
to
Windows 8.x
.
4. Press
[F4]
to save the settings and exit the BIOS setup.
The device is restarted.
ð
Following the restart, the Windows drivers for the serial interfaces are loaded. The serial interfaces are
thus ready for operation with Windows 10. And immediately no longer function with TwinCAT.